White Rodgers CZ-4 Master Zone Control Panel Design Guide
www.white-rodgers.com
237
TECHNICAL HELP
ZONING
DESIGN
ZONING SYSTEM DESIGN
Zoning any forced air system is easy once you know a few of the ba-
sic rules. The main consideration is to maintain a constant amount of
air flow (CFM) through the HVAC Unit. This needs to occur when only
one zone is open and if the zones are of varying size when the small-
est zone is open. The other consideration is not to oversize a duct
system too much in order to maintain adequate velocity and airflow
when all zones are open and may be calling for conditioning on those
design temperature days.
The design of the duct system for today’s zoning is an important
factor to a comfortable and efficient zoning system. The number of
zones, along with their size, often determine the best type of design.
There are scenarios for zoning. The first, which is typically on new
installations where the duct work can be designed for zoning would
be to oversize the ducts for each zone in order to get more air to the
zone when it may be the only one calling. The scenario for all others
would be to use a by-pass damper to relieve the excess air pressure
in the duct system when a minority number of zones are calling.
The reason for each zone duct being the same size is that any zone
could be the only zone calling and therefore that zone must handle
the CFM of the HVAC Unit. When the duct is sized for 2/3 of the total
CFM the smaller size does restrict the airflow and forces the air at
a higher pressure and velocity, however it does not increase the air
typically over that static pressure rating of the blower motor, usually
0.5”W.C. This also keeps the air velocity from being noticeably noisy.
Below is a quick guide to determine the minimum equivalent size of a
zone duct for each size HVAC Unit.
Systems over 5 Tons typically are commercial and would use a by-
pass damper to relieve the excess air pressure when the majority of
zones shut down.
In retrofit and systems with 4 zones or more, over sizing the ducts is
not practical. In these instances a by-pass damper is used to relieve
the excess air back into the return air duct or dump the air into a
central area of the building, such as a hallway, where often there is
a common return. In this instance try to locate the by-pass air as far
away from the return air intake as possible.
In new installations where ducts are being added it is recommended
to size each zone duct the same and to size the duct for approximate-
ly 2/3 of the total HVAC System CFM. This is practical on systems
with 2 or 3 zones and when all zones are approximately equal in size.
This is NOT practical in an installation where 80% of conditioned area
is one zone and 20% is the other zone.
The key to a good zoning system is to deliver the conditioned air to
the calling zone as fast and quietly as possible in order to satisfy the
demand. Whatever air cannot be directed into the zone must then by
by-passed. This develops the formula for calculating the size of the
by-pass damper.
T
otal CFM - Smallest Zone CFM = By-Pass CFM
Once the amount of by-pass air is known it is just common sense to
size a duct adequately to handle the amount of air. White-Rodgers
has both round and rectangular/square by-pass damper sizes.
Also See for White Rodgers CZ-4 Master Zone Control Panel
Related Manuals for White Rodgers CZ-4 Master Zone Control Panel
-
White Rodgers Zoninc & Indoor Air Quality CAZ-2 Zone Plus Control Panel Design Guide
4 pages
-
White Rodgers Zoninc & Indoor Air Quality CMM-3U Zone Control Panel Design Guide
4 pages
-
White Rodgers Zoninc & Indoor Air Quality CMM-3UK Zone Control Panel Design Guide
4 pages
-
White Rodgers Zoninc & Indoor Air Quality CZ-4K Master Zone Control Panel Design Guide
4 pages