White Rodgers 3L09 User's Manual

White Rodgers Heating System User's Manual - 3L09.
Download
Page  of 1
4.4, 1039 votes
background image

To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.

Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper
and dangerous operation.

Following installation or replacement, follow
appliance manufacturers’ recommended instal-
lation/service instructions to insure proper op-
eration.

PART NO. 37-6133A

9949

Printed in U.S.A.

DESCRIPTION

This series of limit controls has a normally closed SPST
switch that opens on temperature rise to limit the maxi-
mum allowable temperature in forced air heating sys-

PRECAUTIONS

THIS CONTROL MUST BE INSTALLED BY A QUALI-
FIED INSTALLER.

All wiring must conform to local and national electrical
codes and ordinances.

This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.

This control has been accurately calibrated at the factory.
Any attempt to re-calibrate this control will void the White-
Rodgers warranty.

Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.

If in doubt about whether your wiring is millivolt,
low or line voltage, have it inspected by a quali-
fied heating and air conditioning contractor or a
licensed electrician.

CAUTION

!

tems. A small bimetal sensing element is located in the air
stream for quick response. These controls have a fixed
temperature setting and fixed differential.

WARNING

!

SPECIFICATIONS

ELECTRICAL RATING:

Resistive: 15 amps @ 120 VAC

13 amps @ 240 VAC
9.3 amps @ 277 VAC

Inductive: 5.8 FLA, 34.8 LRA @ 120 VAC

2.9 FLA, 13.0 LRA @ 240 VAC

Pilot Duty: 278 VA

Temperature Setting:

Fixed setting stamped on control

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398

3L09

Limit Controls

WHITE-RODGERS

INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

This control must be mounted in the air stream of the
appliance. Follow the original equipment manufacturers’
recommendations for proper location and wiring.

Wiring

All wiring must conform to local and national

electrical codes and ordinances.

INSTALLATION