White Rodgers 24A34-3 Electric Heat Sequencer Catalog Page

White Rodgers Heaters Catalog Page - 24A34-3 Electric Heat Sequencer.
Download
Page  of 1
4.5, 1106 votes
background image

 

Model 

 

 

Timings – ON 

Timings – OFF

  Number 

Timings  Switches M1-M2  M3-M4  M5-M6  M7-M8  M9-M10  M1-M2  M3-M4  M5-M6  M7-M8  M9-M10

 

24A34-1 

1-20 

– 

– 

– 

– 

40-110 

– 

– 

– 

 

24A34-2 

– 

– 

30-90 

– 

– 

– 

– 

1-30 

– 

 

24A34-3 ➀ 

1-20  1-20 

– 

– 

– 

40-110

  40-110 

– 

– 

 

24A34-4 

– 

– 

30-90  30-90 

– 

– 

– 

1-30  1-30 

 

24A34-5 ➀ 

1-110  1-110  1-110 

– 

– 

1-110  1-110  1-110 

– 

 

24A34-6 ➀ 

1-110  1-110  1-110  1-110 

– 

1-110  1-110  1-110  1-110 

 

24A34-14➀➁ 

1-160  1-160  1-160  1-160  1-160  1-160  1-160  1-160  1-160  1-160

 

24A34-21 

1-20 

– 

– 

– 

– 

1-50 

– 

– 

– 

 

24A34-22 

15-45 

– 

– 

– 

– 

1-30 

– 

– 

– 

 

24A34-23 

25-55 

– 

– 

– 

– 

15-45 

– 

– 

– 

 

24A34-24 

30-75 

– 

– 

– 

– 

1-40 

– 

– 

– 

 

24A34-25 

40-90 

– 

– 

– 

– 

1-30 

– 

– 

– 

 

24A34-26 

1-20  30-90 

– 

– 

– 

40-90  1-30 

– 

– 

 

24A34-27 

1-160  1-160 

– 

– 

– 

1-160  1-160 

– 

– 

 

24A34-28 ➂ 

1-160  1-160 

– 

– 

– 

1-160  1-160 

– 

– 

 

24A34-29 

15-35 

– 

– 

– 

– 

25-55 

– 

– 

– 

 

24A34-36 

1-20  30-45 

– 

– 

– 

45-110  1-30 

– 

– 

 

24A34-37 

1-110 

– 

– 

– 

– 

1-110 

– 

– 

– 

MODEL 24A34 ELECTRIC HEAT SEQUENCERS

DirectReplacementforMostFan/HeatSequencingFunctions.

TerminalMarkingsareEquivalenttoCompetitiveTypes
FEATURES
•ReplacesHoneywell,MARS,TOD,

  GEMLINE, Klixon (Texas Instruments).

•24Vinputcontrol.

•Multi-poisemounting.

 

 

Resistive (Non-Inductive) 

Motor Ratings (Inductive)

 

VAC 

Watts 

Amps 

Full Load 

Locked Rotor 

Pilot Duty

 

120 

3000 

25.0 

14.0A 

72.0A 

125 VA

 

240 

6000 

25.0 

7.0A 

42.0A 

125 VA

 

480 

6000 

12.5 

– 

– 

480 VA

ELECTRICAL RATINGS – SINGLE LOAD CONTACT RATINGS (ALL MODELS)

•Anycontacts(exceptM1&M2)canbe

  used as auxiliary contacts.

•Doublequick-connectterminalsfor

  combination loads.

SPECIFICATIONS
Ambient Temperature Rating . . . . . . . . . .   -50 to +165°F

Agency . . . . . . . . . . . . . . . . . . . . . . . . . . .   U.L. component recognized

TABLE NOTES:

 M1-M2andM3-M4arealwaysfirstswitches

  to turn ON and last to turn OFF. All other

  switches are random ON and random OFF

  24A34-14 Switch contacts designated 

  F1 -  F2 instead of M1 - M2

  24A34-28 is 2 pole double throw

  These contacts switch simultaneously

NOTE:UnderwritersLaboratoriesrequiresa

faninterlockcircuittoinsuretheblower

remains operating whenever more than one 

sequencerisused.Thefaninterlockshould

be the M1 / M2 contacts of the second or third 

sequencer.

All M1 / M2 contacts are wired to the blower mo-

torsothatanysequencerthatisenergizedwill

keeptheblowerON.

COMBINED LOAD RATING TABLE

(ALL MODELS)
30A @ 240 VAC – TOTAL,

23A Non-Inductive + 7 FLA / 42 LRA Inductive,

ONTime: Elapsedtimetomakecontactsafter

 

heater is energized (min. to max.)

OFFTime: Elapsedtimetobreakcontactsafter

 

heater is de-energized (min. to max.)





24A34-3

  Model 

 

 

Timings

  Number 

Timings 

Switches 

ON 1-3 

OFF 1-3

 

24A34-15 

1-60 

75-95

24A34-15 HEAT PUMP CONTROL
FEATURES
•Usedinheatpumpairhandlerapplications.

•Providesadelayofftotheblowermotorincoolingmode.

•Singlepoledoublethrow.

 

 

Resistive (Non-Inductive) 

Motor Ratings (Inductive)

 

VAC 

Watts 

Amps 

Full Load 

Locked Rotor 

Pilot Duty

 

120 

3000 

25.0 

14.0A 

72.0A 

125 VA

 

240 

6000 

25.0 

7.0A 

42.0A 

125 VA

ELECTRICAL RATINGS – NORMALLY OPEN CONTACTS 1-3

 

 

Resistive (Non-Inductive)

 

VAC 

Watts 

Amps 

Pilot Duty

 

120 

1200 

10.0 

125 VA

 

240 

1200 

5.0 

125 VA

ELECTRICAL RATINGS – NORMALLY CLOSED CONTACTS 1-2

ELECTRIC HEAT

PRODUCTS

Indicates Canadian Model Number: call 1-800-305-6953 to order

HEA

TING

www.white-rodgers.com

71

Also See for White Rodgers 24A34-3 Electric Heat Sequencer

Related Manuals for White Rodgers 24A34-3 Electric Heat Sequencer

0.743509s