White Rodgers 24A34-23 Electric Heat Sequencer Catalog Page
Model
Timings – ON
Timings – OFF
Number
Timings Switches M1-M2 M3-M4 M5-M6 M7-M8 M9-M10 M1-M2 M3-M4 M5-M6 M7-M8 M9-M10
24A34-1
1
1
1-20
–
–
–
–
40-110
–
–
–
–
24A34-2
1
1
–
–
30-90
–
–
–
–
1-30
–
–
24A34-3 ➀
1
2
1-20 1-20
–
–
–
40-110
40-110
–
–
–
24A34-4
1
2
–
–
30-90 30-90
–
–
–
1-30 1-30
–
24A34-5 ➀
2
3
1-110 1-110 1-110
–
–
1-110 1-110 1-110
–
–
24A34-6 ➀
2
4
1-110 1-110 1-110 1-110
–
1-110 1-110 1-110 1-110
–
24A34-14➀➁
4
5
1-160 1-160 1-160 1-160 1-160 1-160 1-160 1-160 1-160 1-160
24A34-21
1
1
1-20
–
–
–
–
1-50
–
–
–
–
24A34-22
1
1
15-45
–
–
–
–
1-30
–
–
–
–
24A34-23
1
1
25-55
–
–
–
–
15-45
–
–
–
–
24A34-24
1
1
30-75
–
–
–
–
1-40
–
–
–
–
24A34-25
1
1
40-90
–
–
–
–
1-30
–
–
–
–
24A34-26
2
2
1-20 30-90
–
–
–
40-90 1-30
–
–
–
24A34-27
2
2
1-160 1-160
–
–
–
1-160 1-160
–
–
–
24A34-28 ➂
2
2
1-160 1-160
–
–
–
1-160 1-160
–
–
–
24A34-29
1
1
15-35
–
–
–
–
25-55
–
–
–
–
24A34-36
2
2
1-20 30-45
–
–
–
45-110 1-30
–
–
–
24A34-37
1
1
1-110
–
–
–
–
1-110
–
–
–
–
MODEL 24A34 ELECTRIC HEAT SEQUENCERS
DirectReplacementforMostFan/HeatSequencingFunctions.
TerminalMarkingsareEquivalenttoCompetitiveTypes
FEATURES
•ReplacesHoneywell,MARS,TOD,
GEMLINE, Klixon (Texas Instruments).
•24Vinputcontrol.
•Multi-poisemounting.
Resistive (Non-Inductive)
Motor Ratings (Inductive)
VAC
Watts
Amps
Full Load
Locked Rotor
Pilot Duty
120
3000
25.0
14.0A
72.0A
125 VA
240
6000
25.0
7.0A
42.0A
125 VA
480
6000
12.5
–
–
480 VA
ELECTRICAL RATINGS – SINGLE LOAD CONTACT RATINGS (ALL MODELS)
•Anycontacts(exceptM1&M2)canbe
used as auxiliary contacts.
•Doublequick-connectterminalsfor
combination loads.
SPECIFICATIONS
Ambient Temperature Rating . . . . . . . . . . -50 to +165°F
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. component recognized
TABLE NOTES:
➀
M1-M2andM3-M4arealwaysfirstswitches
to turn ON and last to turn OFF. All other
switches are random ON and random OFF
➁
24A34-14 Switch contacts designated
F1 - F2 instead of M1 - M2
➂
24A34-28 is 2 pole double throw
♦
These contacts switch simultaneously
NOTE:UnderwritersLaboratoriesrequiresa
faninterlockcircuittoinsuretheblower
remains operating whenever more than one
sequencerisused.Thefaninterlockshould
be the M1 / M2 contacts of the second or third
sequencer.
All M1 / M2 contacts are wired to the blower mo-
torsothatanysequencerthatisenergizedwill
keeptheblowerON.
COMBINED LOAD RATING TABLE
(ALL MODELS)
30A @ 240 VAC – TOTAL,
23A Non-Inductive + 7 FLA / 42 LRA Inductive,
ONTime: Elapsedtimetomakecontactsafter
heater is energized (min. to max.)
OFFTime: Elapsedtimetobreakcontactsafter
heater is de-energized (min. to max.)
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
♦
24A34-3
Model
Timings
Number
Timings
Switches
ON 1-3
OFF 1-3
24A34-15
1
1
1-60
75-95
24A34-15 HEAT PUMP CONTROL
FEATURES
•Usedinheatpumpairhandlerapplications.
•Providesadelayofftotheblowermotorincoolingmode.
•Singlepoledoublethrow.
Resistive (Non-Inductive)
Motor Ratings (Inductive)
VAC
Watts
Amps
Full Load
Locked Rotor
Pilot Duty
120
3000
25.0
14.0A
72.0A
125 VA
240
6000
25.0
7.0A
42.0A
125 VA
ELECTRICAL RATINGS – NORMALLY OPEN CONTACTS 1-3
Resistive (Non-Inductive)
VAC
Watts
Amps
Pilot Duty
120
1200
10.0
125 VA
240
1200
5.0
125 VA
ELECTRICAL RATINGS – NORMALLY CLOSED CONTACTS 1-2
ELECTRIC HEAT
PRODUCTS
Indicates Canadian Model Number: call 1-800-305-6953 to order
HEA
TING
www.white-rodgers.com
71
Related Manuals for White Rodgers 24A34-23 Electric Heat Sequencer
-
Desa Tech Heaters SPC-200C Owner's Manual
12 pages
-
Desa Tech Heaters CGFB32CA Owner's Manual
16 pages
-
Desa Tech Heaters LMFP33NRA Owner's Manual
36 pages
-
Desa Tech Heaters LMFP33PRA Owner's Manual
36 pages
-
Desa Tech Heaters LMFP33PRB Owner's Manual
36 pages
-
Desa Tech Heaters T36NR Owner's Manual
36 pages
-
Desa Tech Heaters V36NS-A Owner's Manual
36 pages
-
Carrier Heaters WEATHERMAKER 8000 58WAV Owner's Manual
24 pages
-
BENDIX Heaters AD-IP INTEGRAL PURGE AIR DRYER User's Manual
28 pages
-
White Rodgers Heaters 21V51U-843 Universal Two-stage HSI Integrated Furnace Control Kit Catalog Page
1 pages
-
White Rodgers Heaters 3098-134 Mercury Flame Sensors Reference Guide
1 pages
-
White Rodgers Heaters 36C03-300 Gas Valve Installation Instructions
24 pages
-
White Rodgers Heaters 36C03-300 Gas Valve Supplemental Wiring
4 pages
-
White Rodgers Heaters 36C03-333 Gas Valve Installation Instructions
24 pages
-
White Rodgers Heaters 36C03-400 Gas Valve Installation Instructions
24 pages
-
White Rodgers Heaters 36G22-254 36G Series Gas Valve Installation Instructions
8 pages
-
White Rodgers Heaters 50A55-843 Universal Silicon Carbide Integrated Furnace Control Catalog Page
1 pages
-
White Rodgers Heaters 50A55-843 Universal Silicon Carbide Integrated Furnace Control Specification Sheet
2 pages
-
White Rodgers Heaters 50A55-843 Universal Silicon Carbide Integrated Furnace Control Wiring diagram
2 pages
-
White Rodgers Heaters 770-1 Dual Purpose Air Switch Catalog Page
1 pages
-
White Rodgers Heaters 8A04-1 SPDT Fan Relays Catalog Page
1 pages
-
Trane Heaters Gas Unit Heaters Installation and Maintenance Manual
44 pages
-
Trane Heaters Electric Unit Heaters Catalogue
48 pages
-
Duraflame Heaters 10HM8000 Operation instructions manual
9 pages