White Rodgers 1F95-1291 User's Manual

White Rodgers Thermostats User's Manual - 1F95-1291.
Download
Page  of 16
4.6, 1924 votes
background image

Model

Programming Choices

1F95-1291

7 Day

5/1/1 Day

Non-Programmable

www.white-rodgers.com

Big Blue Humidity Universal Thermostat 

with Humidity/Dehumidity Control and 

Automatic Heat/Cool Changeover Option

PART NO. 37-6914D

Replaces 37-6914C

0905

Single Stage, Multi-Stage, Heat Pump

Installation and Operating Instructions

APPLICATIONS

1F95-1291 Humidity Control Touchscreen Thermostat

SPECIFICATIONS

Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS 
CAREFULLY BEFORE INSTALLING OR OPERATING THIS 
CONTROL COULD CAUSE PERSONAL INJURY AND/OR 
PROPERTY DAMAGE.

THERMOSTAT APPLICATION GUIDE

Thermostat 

Confi guration Options

Thermostat 

Applications

Maximum 

Stages

Heat/Cool

Single Stage 1

No Heat Pump (SS1)

Gas, Oil, Electric, Heat Only, 

Cool Only or Heat/Cool 

Systems, 2 or 3 wire Hydronic 

Zone (Hot Water or Steam) 

Systems, 24 Volt or Millivolt

1/1

Multi Stage 2

No Heat Pump (MS2)

2/2

Heat Pump 1

Single Stage Compressor 

Heat Pump (HP1)

Single Stage Compressor 

Heat Pump Systems - up to 2 
Stages Aux./Emergency Heat

3/1

Heat Pump 2

Two Stage or Two

Compressor Heat Pump 

(HP2)

Two Stage or Two Compressor 

Heat Pump systems - up to 2 

Stages Aux./Emergency Heat

4/2

ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.

Mercury and products containing mercury must not be 
discarded in household trash. Do not touch any spilled 
mercury. Wearing non-absorbent gloves, clean up any 
spilled mercury and place in a sealed container. For proper 
disposal of a product containing mercury or a sealed 
container of spilled mercury, place it in a suitable shipping 
container. Refer to www.white-rodgers.com for location to 
send the product containing mercury.

Index

Page

Installation

2

Wiring Diagrams

3

Thermostat Quick Reference

5

Installer Confi guration Menu

6

Operating Your Thermostat

10

Programming

12

Troubleshooting

16

Electrical Rating:
 

Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . .    mV to 30 VAC, NEC Class II, 50/60 Hz or DC

 

Input-Hardwire  . . . . . . . . . . . . . . . . . . . . . . . . .    20 to 30 VAC

Terminal Load  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . .    45 to 99°F (7 to 32°C)
Differential (Single Stage)  . . . . . . . . . . . . . . . . . . . .    Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage)  . . . . . . . . . . . . . . . . . . . . .    Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump)  . . . . . . . . . . . . . . . . . . . . .    Heat 1.2°F; Cool 1.5°F
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . .    32°F to +105°F (0 to +41°C)
Operating Humidity  . . . . . . . . . . . . . . . . . . . . . . . . .    90% non-condensing max.
Shipping Temperature Range  . . . . . . . . . . . . . . . . .    -40 to +150°F (-40 to +65°C)
Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . .    4.6"H x 5.9"W x 1.2"D

To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.

CAUTION

!