White Rodgers 1F95-0680 User's Manual

White Rodgers Thermostats User's Manual - 1F95-0680.
Download
Page  of 16
4.9, 1026 votes
background image

Blue Commercial Thermostat with 

Automatic Heat/Cool Changeover 

Option and Damper Control

Model

Programming Choices

1F95-0680

7 Day

5/1/1 Day

Non-Programmable

www.white-rodgers.com

PART NO. 37-6819A

0811

Single Stage, Multi-Stage, Heat Pump

Installation and Operating Instructions for Model:

APPLICATIONS

THERMOSTAT APPLICATION GUIDE

1F95-0680 Commercial Thermostat

SPECIFICATIONS

To prevent electrical shock and/or equipment damage, 
disconnect electric power to system at main fuse or 
circuit breaker box until installation is complete.

CAUTION

!

Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS 
CAREFULLY BEFORE INSTALLING OR OPERATING THIS 
CONTROL COULD CAUSE PERSONAL INJURY AND/OR 
PROPERTY DAMAGE.

Description

Heat Pump (No Aux. or Emergency Heat)

Yes

Heat Pump (with Aux. or Emergency Heat)

Yes

Systems with up to 4 Stages Heat, 2 Stages Cool

Yes

Heat Only Systems

Yes

Millivolt Heat Only Systems – Floor or Wall Furnaces

Yes

Cool Only Systems

Yes

Gas or Oil Heat

Yes

Electric Furnace

Yes

Hydronic (Hot Water) Zone Heat – 2 Wires

Yes

Hydronic (Hot Water) Zone Heat – 3 Wires

Yes

Wired Remote Temperature Sensor (Indoor or Outdoor)

Yes

Dual Fuel Damper Control Feature (Heat Pump Mode 
Outdoor Remote Required)

Yes

ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.

Mercury and products containing mercury must not be 
discarded in household trash. Do not touch any spilled 
mercury. Wearing non-absorbent gloves, clean up any 
spilled mercury and place in a sealed container. For proper 
disposal of a product containing mercury or a sealed 
container of spilled mercury, place it in a suitable shipping 
container. Refer to www.white-rodgers.com for location to 
send product containing mercury.

Index

Page

Installation

2

Wiring Connections

2

Wiring Diagrams

3

Thermostat Quick Reference

4

Installer Confi guration Menu

5

Operating Your Thermostat

8

Programming

9

Troubleshooting

13

Electrical Rating:
 

Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . .    mV to 30 VAC, NEC Class II, 50/60 Hz or DC

 

Input-Hardwire  . . . . . . . . . . . . . . . . . . . . . . . . .    20 to 30 VAC

Terminal Load  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . .    45 to 99°F (7 to 32°C)
Differential (Single Stage)  . . . . . . . . . . . . . . . . . . . .    Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage)  . . . . . . . . . . . . . . . . . . . . .    Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump)  . . . . . . . . . . . . . . . . . . . . .    Heat 1.2°F; Cool 1.5°F
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . .    32°F to +105°F (0 to +41°C)
Operating Humidity  . . . . . . . . . . . . . . . . . . . . . . . . .    90% non-condensing max.
Shipping Temperature Range  . . . . . . . . . . . . . . . . .    -40 to +150°F (-40 to +65°C)
Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . .    4.2"H x 6.4"W x 1.7"D

0.483969s