background image

Structure and Operation

3

Structure and Operation

Modular structure

The complete control consists of a

control base, control unit

(electronic/operating modules) and a

Power/Pump Module.

The control unit comprises:

Power on/off switch, an electronic high

limit, a temperature gage and a low

temperature control

adjustable high limit

fixed high limit

TUV test switch, override switch,

buttons for:

holiday program

party and economy modes

reduced operating mode temperature

domestic hot water temperature

programming of heating curves for

boiler water temperature and/or mixing

valve circuit temperature

heating circuit selection,

a selector knob for normal operating

temperatures and a digital timer.

Heat-demand-controlled circuit pump and

burner activation, adjusting of a variable

temperature limit, pump cycling,

integrated diagnostic system and flue gas

monitoring in connection with flue gas

temperature sensor (optional) and

maintenance display.

Boiler-specific functions

The Vitotronic control modulates the

boiler water temperature.

It gradually regulates the boiler water

temperature (= the supply temperature

of the direct-connected heating circuit) as

well as the supply water temperature of a

mixing valve circuit. The control contains

an adaptive tank temperature control

logic with priority switching (heat pump

off, mixing valve closed).

An additional function for domestic hot

water heating (short-term heating to an

increased temperature) can be selected.

The Vitotronic 200 is an ideal control

option for your heating system with

mixing valve circuit. It is the perfect

solution for your underfloor heating

circuit with supply and return water

temperature sensor or for controlled

drying of a concrete floor.

Control characteristics

Boiler circuit control unit (high

temperature)

Heating circuit control with mixing

valve

Dead zone: ±1.80 ºF/1 ºC

Adjustable high limit factory default

setting:

167 ºF/75 ºC

Adjustment of the fixed high limit:

230 ºF/110 ºC

adjustable to

212 ºF/100 ºC

Adjustment range of heating curve:

Slope:

0.2 to 3.5

Shift:

–23 ºF to +72 ºF/

–13 ºC to +40 ºC

High limit:

68 to 266 ºF/

20 to 130 ºC

Low limit:

34 to 261 ºF/

1 to 127 ºC

Differential temperature for heating

circuit with mixing valve: 0 to 72 ºF/

0 to 40 ºC

Adjustment range for domestic hot

water setpoint temperature:

50 to 140 ºF/

10 to 60 ºC

adjustable to

50 to 203 ºF/

10 to 95 ºC

Technical data

Rated voltage:

120 VAC

Rated frequency:

60 Hz

Rated current:

6 A

Power consumption:

5 W

Maximum ambient

temperature

at operation:

32 to 104 ºF/

0

to 40 ºC

(in rooms and

installation sites

with normal

ambient

conditions)

when storing or transporting:

–4 to +149 ºF/

–20 to +65 ºC

Relay output rating in conjunction with a

Power/Pump Module:

Heating circuit

pumps:

3 FLA/120 VAC*1

DHW tank heating

circulation pump: 3 FLA/120 VAC*1

Domestic hot water

recirculation pump:3 FLA/120 VAC*1

Mixing valve

actuator:

0.1 FLA/120 VAC*1

Operating time approx. 2 minutes

Burner plug

:

2 FLA/120 VAC

2-stage burner

plug

*2:

0.5 FLA/120 VAC

Total:

max. 12 A/120 VAC

*1Total 12 A/120 VAC

*2Available only with extension module

for 2-stage burner (included in boiler

package).

Boiler coding card

Adapts the control to the specific boiler

model being used (included in boiler

package).

Connections

Sensors, burner and Power/Pump

Module are connected to the back of

the control unit via system plugs.

Pumps, power supply and mixing valve

are connected to the Power/Pump

Module via screw terminals or system

plugs.

Operating unit

With digital timer

Clear text LCD display

Temperature and fault display

Coding via display of operating unit

All adjustments and basic coding

information in clear text format.

5167

888

v1

.1