TOSHIBA G3 APPLICATION GUIDELINE 21.5 

*  For additional assistance, please contact Toshiba at (800) 231-1412 and ask for inverter marketing 

Direction Change with RX Input (page 1 of 2) 

 
Introduction

 

Like all speed references on the G3, the RX input has an adjustable bias and gain. The RX is unique, however, in that its inputs can be 
positive or negative and the corresponding speeds can be positive or negative. The first example shown below will allow a motor 
direction change based on a positive-only speed reference (a speed pot). The second example will illustrate how to program the drive 
to accept an input that reverses polarity. If you do not have a motor connected, use monitor to verify direction change. Set SWITCH 1 
(right of the phone jack on the control board under the keypad) to ‘5’ or ‘10’ as appropriate for the voltage you are applying to the RX 
terminal. The I/V switch does not apply to the RX terminal.  
 
Connections for positive-only reference 
 

                                                                                       

TERMINAL STRIP 

 
 
 
                                ST                  CC                                                                                                            F                   CC 
 
 
                                                                                                               PP               RX               CC 
 
 
 
 
 
 
Example programming for positive-only reference 

Group 

Parameter 

New Value 

UTILITY PARAMETERS 

Blind Function Selection 

UTILITY PARAMETERS 

Frequency Setting Parameters Blind 

FREQUENCY SETTING PARAMETERS 

Frequency Priority Selection #1 

FREQUENCY SETTING PARAMETERS 

RX Terminal Standard or Adjustable 

FREQUENCY SETTING PARAMETERS 

RX Reference Setting Point #1 

0 (default) 

FREQUENCY SETTING PARAMETERS 

RX Point #1 Frequency 

60 

FREQUENCY SETTING PARAMETERS 

RX Reference Setting Point #2 

100 (default) 

FREQUENCY SETTING PARAMETERS 

RX Point #2 Frequency 

-60 