Toshiba 15-80KVA User's Manual
TOSHIBA 4200FA UPS
Installation Planning Guide for 15-80kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev. 1.03
Page 1 of 2
4200FA-IPG-208v
General Mechanical Information
Dimensions
(W x D x H)
Weight
Approximate Full-Load Heat Loss
UPS kVA/ kW Rating
Inches
Lbs.
kBtu/Hr
15 kVA/12 kW
20 x 36.25 x 59.85
900
5.7
25 kVA/ 20 kW
20 x 36.25 x 59.85
910
7.6
30 kVA/ 24 kW
20 x 36.25 x 59.85
915
9.1
50 kVA/ 40 kW
35.59 x 38.19 x 59.39
2,548
17.7
80 kVA/ 64 kW
44 x 31 x 74
1,560
40.0
Primary AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
>0.97
45.7
60 AT
(1) x 8 / (1) x 6
380
25
>0.97
76.3
90 AT
(1) x 4 / (1) x 2
380
30
>0.97
92.4
125 AT
(1) x 3 / (1) x 1
380
50
>0.97
152.6
200 AT
(1) x 1/0 / (1) 4/0
380
80
>0.97
244.3
300 AT
(1) x 300 / (1) x 500
380
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG at 75º C Temp. Rating
Feet
15
>0.97
41.6
60 AT
(1) x 8 / (1) x 6
380
25
>0.97
69.4
90 AT
(1) x 4 / (1) x 2
380
30
>0.97
83.3
110 AT
(1) x 3 / (1) x 1
380
50
>0.97
138.8
175 AT
(1) x 1/0 / (1) 4/0
380
80
>0.97
222.1
300 AT
(1) x 4/0 / (1) x 400
380
Battery Input (288VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
13.33
61.7
90 AT
(1) x 6
70
25
22.22
102.8
125 AT
(1) x 2
70
30
26.67
123.0
175 AT
(1) x 1
70
50
44.44
205.7
225 AT
(1) x 4/0
70
80
71.11
329.2
400 AT
(2) x 3/0
70
AC Output (208/120V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
0.8
41.6
60 AT
(1) x 8 / (1) x 6
380
25
0.8
69.4
90 AT
(1) x 4 / (1) x 2
380
30
0.8
83.3
110 AT
(1) x 3 / (1) x 1
380
50
0.8
138.8
175 AT
(1) x 1/0 / (1) 4/0
380
80
0.8
222.1
300 AT
(1) x 4/0 / (1) x 400
380
Related Manuals for Toshiba 15-80KVA
-
APC Power Supply ES 550 User's Manual
2 pages
-
Yamaha Power Supply PSR-270 Owner's Manual
120 pages
-
CyberPower Power Supply CP1500PFCLCD User's Manual
2 pages
-
LG Power Supply SV-iC5 Series User's Manual
141 pages
-
Siemens Power Supply MICROMASTER 440 User's Manual
78 pages
-
APC Power Supply AP8941 User's Manual
128 pages
-
APC Power Supply Back UPS BR1500LCD User's Manual
3 pages
-
APC Power Supply Back UPS BX1300LCD User's Manual
3 pages
-
APC Power Supply Back-UPS BX1500G User's Manual
10 pages
-
APC Power Supply BACK-UPS PRO 1200/1500 User's Manual
8 pages
-
APC Power Supply BACK-UPS PRO 1300 User's Manual
8 pages
-
APC Power Supply BACK-UPS PRO 1500 User's Manual
21 pages
-
APC Power Supply BACK-UPS PRO BR1500G User's Manual
8 pages
-
APC Power Supply BACK-UPS RS 1000 User's Manual
2 pages
-
APC Power Supply BACK-UPS RS 800 User's Manual
2 pages
-
APC Power Supply MGE GALAXY PW 20 - 200 KVA User's Manual
40 pages
-
APC Power Supply Smart UPS 1000XL User's Manual
18 pages
-
APC Power Supply Smart UPS 750XL User's Manual
18 pages
-
APC Power Supply Smart UPS SUA1500 User's Manual
17 pages
-
Schneider Electric Power Supply MGE GALAXY 5000 User's Manual
17 pages
-
Dell Power Supply 1920W User's Manual
73 pages
-
HP Power Supply HP T1500 G3 User's Manual
38 pages
-
MGE UPS Systems Power Supply PULSAR 1500 RT2U User's Manual
126 pages
-
MGE UPS Systems Power Supply PULSAR M 3000 RT 2U User's Manual
24 pages