TOSHIBA 4200FA UPS 

Installation Planning Guide for 15-80kVA UPS 

Standard System: 208/120V Input, 208/120V Output 

Rev. 1.03 

Page 1 of 2 

4200FA-IPG-208v 

 
 

General Mechanical Information 

Dimensions 

 (W  x D x H) 

Weight 

Approximate Full-Load Heat Loss 

UPS kVA/ kW Rating 

Inches 

Lbs. 

kBtu/Hr 

15 kVA/12 kW 

20 x 36.25 x 59.85 

900 

5.7 

25 kVA/ 20 kW 

20 x 36.25 x 59.85 

910 

7.6 

30 kVA/ 24 kW 

20 x 36.25 x 59.85 

915 

9.1 

50 kVA/ 40 kW 

35.59 x 38.19 x 59.39 

2,548 

17.7 

80 kVA/ 64 kW 

44 x 31 x 74 

1,560 

40.0 

 

Primary AC Input (208/120V 3-Phase / 4-Wire) 

Maximum Input Power 

Demand 

Suggested External 

Overcurrent Protection 

Suggested Minimum Feeder 

Wire Size Per Phase / Neutral 

Suggested Maximum Feeder Length 

For Min. Wire Size in Steel Conduit 

kVA 

PF 

Amps 

Amps 

AWG or kcmil at 75º C Temp. Rating 

Feet 

15 

>0.97 

45.7 

60 AT 

(1) x 8 / (1) x 6 

380 

25 

>0.97 

76.3 

90 AT 

(1) x 4 / (1) x 2 

380

 

30 

>0.97 

92.4 

125 AT 

(1) x 3 / (1) x 1 

380

 

50 

>0.97 

152.6 

200 AT 

(1) x 1/0 / (1) 4/0 

380

 

80 

>0.97 

244.3 

300 AT 

(1) x 300 / (1) x 500 

380 

 

Optional Alternate AC Input (208/120V 3-Phase / 4-Wire) 

Maximum Input Power 

Demand 

Suggested External 

Overcurrent Protection 

Suggested Minimum Feeder 

Wire Size Per Phase / Neutral 

Suggested Maximum Feeder Length 

For Min. Wire Size in Steel Conduit 

kVA 

PF 

Amps 

Amps 

AWG at 75º C Temp. Rating 

Feet 

15 

>0.97 

41.6 

60 AT 

(1) x 8 / (1) x 6 

380 

25 

>0.97 

69.4 

90 AT 

(1) x 4 / (1) x 2 

380

 

30 

>0.97 

83.3 

110 AT 

(1) x 3 / (1) x 1 

380

 

50 

>0.97 

138.8 

175 AT 

(1) x 1/0 / (1) 4/0 

380

 

80 

>0.97 

222.1 

300 AT 

(1) x 4/0 / (1) x 400 

380 

 

Battery Input (288VDC Nominal) 

Battery Capacity Required 

for Full Load Output 

Maximum Discharge 

at Full Load Output 

Suggested External 

Overcurrent Protection

Suggested Minimum Feeder 

Wire Size Per Phase 

Suggested Maximum Feeder Length 

For Min. Wire Size in Steel Conduit 

 

kWB 

Amps DC 

Amps 

AWG or kcmil at 75º C Temp. Rating 

Feet 

15 

13.33 

61.7 

90 AT 

(1) x 6 

70 

25 

22.22 

102.8 

125 AT 

(1) x 2 

70 

30 

26.67 

123.0 

175 AT 

(1) x 1 

70 

50 

44.44 

205.7 

225 AT 

(1) x 4/0 

70 

80 

71.11 

329.2 

400 AT 

(2) x 3/0 

70 

 

AC Output (208/120V 3-Phase / 4-Wire) 

Rated Output Power 

Suggested External 

Overcurrent Protection 

Suggested Minimum Feeder 

Wire Size Per Phase / Neutral 

Suggested Maximum Feeder Length 

For Min. Wire Size in Steel Conduit 

kVA 

PF 

Amps 

Amps 

AWG or kcmil at 75º C Temp. Rating 

Feet 

15 

0.8 

41.6 

60 AT 

(1) x 8 / (1) x 6 

380 

25 

0.8 

69.4 

90 AT 

(1) x 4 / (1) x 2 

380 

30 

0.8 

83.3 

110 AT 

(1) x 3 / (1) x 1 

380 

50 

0.8 

138.8 

175 AT 

(1) x 1/0 / (1) 4/0 

380 

80 

0.8 

222.1 

300 AT 

(1) x 4/0 / (1) x 400 

380 

 

0.595396s