All installations and services must be performed by qualified service personnel. 
 

13 

These venting tables also include venting combinations, which apply to common 
venting arrangements of two or more appliances. These requirements as wel  as 
all the installation requirements outlined in this manual for an MHA1/MDA1 
series furnace must be fol owed when an MHA1/MDA1 furnace is common 
vented with another Category I gas appliance. 

 

See also Section II, J, 2, of this manual, “Replacing an Existing Furnace From a 
Common Vent” for information on testing the proper operation of appliances in a 
common vent.  

 

The minimum allowable chimney height is determined by the height of the 
surrounding trees, roof, buildings and terrain. The chimney should extend 24" 
above any surrounding obstructions. In cases where the chimney flue extends to 
the basement floor, the draft can usually be improved by filling the base of the 
chimney with sand to within 12" of the flue pipe after relocating the cleanout 
cover. 

 

 
All joints of the vent must be tightly sealed. The inside of the vent should be free 
of all obstructions. 
 
 

 

2. Replacing An Existing Furnace From a Common Vent 
 

CARBON MONOXIDE POISONING HAZARD 

 

Failure to follow the steps outlined below for each appliance connected to 
the venting system being placed into operation could result in carbon 
monoxide poisoning or death. 

 

When an existing furnace is replaced or removed from a common vent serving 
other appliances, the vent system may now be too large to properly vent the 
remaining appliances only and must be modified accordingly. Failure to correct 
an oversized vent can cause the formation of condensate, leakage or spillage of 
combustion byproducts, which may cause property damage, personal injury, or 
loss of life. 

 

The steps below must be followed with each appliance, which is still connected, 
to the common venting system. Each appliance should be placed in operation, 
while the other appliances remaining connected to the common venting system 
are not in operation. 

 

1.  Seal any unused opening(s) in the common venting system. 
 
2.  Visually inspect the venting system for proper size and horizontal pitch, 

as required in the National Fuel Gas Code, NFPA 54/ANSI Z223.1 – 
2002, or the latest edition. Determine there is no blockage or 