background image

SUBMITTAL SHEET

SYSTEM

INDOOR/OUTDOOR

36XS32A

XS3632/C3632A

CEILING RECESSED (4-WAY) AIR CONDITIONER

                                        

                                                            

GENERAL DATA

(AT 230V)

                                                                                   

POWER   V/PH/HZ

230/208/1/60

Circuit Ampacity, Min. (A)

35

Fuse size, Max.

(A)

35

COMPRESSOR

Rotary-Hermetic

No. used

1

R.L. Amps - L.R. Amps (A)

12.7 -95

Crankcase Heater

-

OUTDOOR FAN - TYPE

Propeller

Dia. (in.) - No. used

18-3/32 - 2

Type Drive - No. speeds

Direct – 2 (AUTO)

No. Poles - RPM (High)

6 - 879

No. Motors - HP   

2 - 110

CAM (High)

3,670

F.L. Amps. 

(A)

1.8

OUTDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Slit Plate - Inner Riffled

Rows - F.P.I.

2 - 12.7

Face Area  (sq.ft.)

11.63

Tube Size  (in.)

3/8

INDOOR FAN - TYPE

Turbo

Dia. & Length  (in.) - No. used 19-9/32 -1

No. speeds

3 & Auto

No. Poles -RPM  (High)

6 - 560

No. Motors - HP

1- 50

CFM (HI/MED/LOW)

980/830/650

F.L. Amps (A)

0.9

INDOOR COIL - TYPE

Aluminum Fin & Copper Pipe

Fin Type - Pipe type

Slit Plate - riffled

Rows - F.P.I.

2 - 14.9

Face Area  (sq. ft.)

5.17

Tube Size  (in.)

3/8

Drain Connection Size (in.)

1-1/4

REFRIGERANT

R22

Lbs. - R22  (O.D. Unit)

9.48

Control

Capillary Tube

Connection

Flare

Line Length,  Max  (ft.)

165

Lift difference, Max  (ft.)

100

Line Size - in. O.D. Discharge

3/8

Line Size - in. O.D. Suction

3/4

DIMENSIONS (in.)

H x

W

x

D

Indoor Unit -Uncrated 14-3/32 x 45-9/32 x 33-27/32

-Crated

12-7/16 x 43-27/32 x 32-25/32(Indoor unit)

4-3/32 x 49-1/2

x 39-11/32(Indoor Grille)

Outdoor unit -Uncrated 48-5/8 x 37

x 13-3/8

-Crated

52 -7/32 x 40

x 16-12/32

WEIGHT

INDOOR

OUTDOOR

Net

(lbs.)

75.0

198.0

Shipping (lbs.)

71.0/29.0(Grille) 223.0

Shipping Volume(cu.ft.)

10.4/4.6 (Grille) 19.8

  

                                                                                            SS36XS32A-2

PERFORMANCE DATA @ ARI STANDARD CONDITIONS 

(230/208V)

COOLING

Total Capacity

(BTU/H)

36,000/35,000

Sensible Capacity (BTU/H)

22,940/22,300

Latent Capacity

(BTU/H)

13,060/12,700

SEER

10.8/11.0

Dehumidification

(Pints/H)

11.9/11.9

Amps

(A)

15.4/16.0

Power Inputs

(W)

3,440/3,250

Outdoor Sound Rating (bels)

7.9

FEATURE

Controls

Microprocessor

Remote Controller

LCD Wireless type

Temperature Control

IC Thermostat

Timer

ON/OFF, 24 hours

Night Setback

Built-In

Air Louver

(Horizontal)

-

(Vertical)

Automatic

Power Failure Automatic Restart

Built-In

Self Diagnosis

N/A

OPTION

Refrigerant Line Set

AP3210BH    (30 ft)

AP3215BH    (50 ft)

Low Ambient Control

Available

Fresh Air Intake

-

Central Remote ON-OFF Control

Available

Airduct Extension

Available

Indoor Frame Extension

N/A

Condensate Drain Pump

RCS5PS4B

Non-Removable Remo-con Bracket

RCS-102WD/RCS-302WD

OPERATING RANGE

Cooling

Indoor Air

Outdoor Air

    Intake Temp.

Intake Temp.

Maximum

95 F DB/71 F WB

115 F DB

Minimum

67 F DB/57 F WB

  67 F DB

CERTIFICATION

                36XS32A

AIRCONDITIONING PRODUCTS