Sanyo 18XS52 User's Manual

Sanyo Air Conditioners User's Manual - 18XS52.
Download
Page  of 3
4.5, 1544 votes
background image

-

1-

SANYO AIR CONDITIONING PRODUCTS

DUCTLESS SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS

SPECIFICATIONS - SECTION 15700

Covers Sanyo System Models > 18XS52, 18XLS52 (See plans for specified models & details)

DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - RECESSED CEILING MOUNT

1) GENERAL SPECIFICATIONS

Furnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s) consisting of an
indoor recessed ceiling mounted evaporator/blower section with four (4) way airflow & matching
outdoor condensing section. System(s) shall bear the ARI label showing that the system(s) is ARI
210 or 240 & 270 Certified. Systems shall be listed by ETL Testing Laboratories and bear the
ETL label. Matching systems shall meet or exceed the minimum, Federally mandated Seasonal
Energy Efficiency Rating (SEER) of 10, as certified by the ARI testing programs. System(s)
indoor & outdoor units will operate at sound levels equal to or below specified system(s) (see
plans). Installation & Owners Manuals shall be provided with each system.

Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper
tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on
both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.

System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-
charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor
units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),
shall be sized, installed & grounded by the installer in conformance with the National Electrical
Code (N.E.C.), local codes, as well as, manufacturer’s instructions.

System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote
controller with LCD display that provides access to all system functions, and transmits room
conditions & programs to the indoor microprocessor every 3 minutes. Infrared remote controller
shall be capable of operating system mounted up to 26’ from the indoor section, according to
manufacturer’s recommendations & instructions. System(s) shall have the capability of continuous
operation in the case of a lost or damaged remote controller, utilizing a factory installed, integral
manual switch in conjunction with the system microprocessor.

1A) System Infrared Remote Controller Functions will include: system mode selection,
programmable temperature control, 24 hour programmable timer, one (1) hour off timer,
automatic three (3) speed indoor fan speed control, constant fan speed selection, night setback
mode, automatic sweep/flap control, user selectable room temperature sensor located on either
infrared remote controller or indoor unit, multiple system control using a single controller.

Related Manuals for Sanyo 18XS52

0.564542s