KBD Series Manual 

 

Additional clearances 
Check to determine whether local codes supersede 
these clearances. 

  Avoid termination locations near a dryer vent. 
  Avoid termination locations near commercial 

cooking exhaust. 

  Avoid termination locations near any air inlets. 

  You must install a vent termination at least 12 

inches above the ground or anticipated snow 
level. 

(0.30 m) between  
terminals at same 
level 

(1.52 m) 
vertically 
between 
terminals 

2"

12"

60"

36"

60"

V

V

(1.52 m) 
between  
terminals at 
different levels 

24"

V

(0.61 m) to wall or parapet 

 

12"

V

V

V

60"

V

RU80e, RU90e, RU98e 

RUC80i, RUC90i, RUC98i 

12"

12"

36"

INSIDE

CORNER

V

V

(0.30 m) between  
terminals at same 
level 

(0.30 m ) to 
an inside 
corner 

 

(0.91 m) to ventilated 
or unventilated soffit 
or eve vent; or to a 
deck or porch 

(1.52 m) vertically 
between terminals 

(50 mm) between 
terminals at same level 

(0.30 m) to an 
inside corner 

The vent for this appliance shall not terminate 
  Over public walkways; or 
  Near soffit vents or crawl space vents or other 

area where condensate or vapor could create a 
nuisance or hazard or cause property damage; or 

  Where condensate or vapor could cause damage 

or could be detrimental to the operation of 
regulators, relief valves, or other equipment. 

Important considerations for locating vent 
termination under a soffit (ventilated or unventilated 
or eave vent; or to a deck or porch) 

  Do not install vent termination under a soffit vent 

such that exhaust can enter the soffit vent 

  Install vent termination such that exhaust and rising moisture 

will not collect under eaves.  Discoloration to the exterior of 
the building could occur if installed too close. 

  Do not install the vent termination too close under the soffit 

where it could present recirculation of exhaust gases back 
into the combustion air intake part of the termination. 