Lux Products LV3 Instruction Manual

Lux Products Line Voltage Thermostat Instruction Manual - LV3.
Download
Page  of 1
4.5, 1097 votes
background image

© COPYRIGHT 2006 LUX PRODUCTS CORPORATION. ALL RIGHTS R E S E R V E D

70

80

90

60

50

OFF

LUX

70

80

90

60

50

LO

LUX

70

60

50

80

90

LO

LUX

Complete, Easy To Read

Installation and Operating Instructions

MECHANICAL LINE VOLTAGE THERMOSTATS

LV1

LV2

LV3

SINGLE POLE: Heating Only

DOUBLE POLE: Heating Only

SINGLE POLE: Cooling Only

ELECTRICAL RATINGS:

22 AMPS @ 125 VAC (2600 W)
22 AMPS @ 250/277 VAC (5000 W)
0.75 HP @ 125 VAC
1.50 HP @ 250/277 VAC

UL LISTED
SETTING RANGE:

50°-90°F (10°-32°C)

ELECTRICAL RATINGS:

22 AMPS @ 125 VAC (2600 W)
22 AMPS @ 250/277 VAC (5000 W)
0.75 HP @ 125 VAC
1.50 HP @ 250/277 VAC

UL LISTED
SETTING RANGE:

50°-90°F (10°-32°C)

ELECTRICAL RATINGS:

22 AMPS @ 125 VAC (2600 W)
22 AMPS @ 250/277 VAC (5000 W)
0.75 HP @ 125 VAC
1.50 HP @ 250/277 VAC

UL LISTED
SETTING RANGE:

50°-90°F (10°-32°C)

NOTE:

Model LV2 is intended for use on 250 or 277 volt heating systems where local codes require that a double line disconnect thermostat be used.  On the LV2 model,

only LINE 1 is broken during normal temperature cycling of this thermostat.  Both LINE 1 and LINE 2 are broken when the dial is turned to the OFF position.

WARRANTY
Limited Warranty: If this unit fails because of defects in materials or workmanship within three years of date of original purchase, LUX Products Corporation will, at its
option, repair or replace it. This warranty does not cover damage by accident, misuse, or failure to follow installation instructions. Implied warranties are limited in
duration to three years from date of original purchase. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not
apply to you. Please return malfunctioning or defective units to the participating retailer from which purchase was made, along with proof of purchase. Please refer to
"TECHNICAL ASSISTANCE" before returning thermostat. Purchaser assumes all risks and liability for incidental and consequential damage resulting from installation
and use of this unit. Some states do not allow the exclusion of incidental or consequential damages, so the above exclusion may not apply to you. This warranty gives
you specific legal rights and you may also have other rights which vary from state to state. Applicable in the U.S.A. only.

TECHNICAL ASSISTANCE
If you have any problems installing or using this thermostat, please carefully and thoroughly review this instruction manual. If you require assistance, please contact our
Technical Assistance Department at 856-234-8803 during regular business hours between 8:00AM and 4:30PM Eastern Standard Time, Monday through Friday. You
can also receive technical assistance online anytime day or night at http://www.luxproducts.com. Our web site offers you answers to the most common technical
questions, and also permits you to email your questions to our technical support staff at your convenience. 

GROUND

WIRE

LINE

LOAD

LINE Voltage

THERMOSTAT

Line 1

Load 1

HEATING

LOAD

LINE 1

GROUND

WIRE

LINE 2

LOAD 1

LOAD 2

LINE Voltage

HEATING

LOAD

THERMOSTAT

Load 2

Line 2

Line 1

Load 1

LINE Voltage

THERMOSTAT

Line 1

Load 1

COOLING

LOAD

GROUND

WIRE

LINE

LOAD

WARNING

All three of the thermostat models shown above control line voltage (125/250 VAC) directly. Do not attempt to install these unless you are completely familiar

with house wiring. If proper precautions are not followed, a risk of electric shock may exist, possibly causing severe injury or death. Disconnect power supply

prior to removing existing thermostat or installing this one. Do not connect to voltages different than the ratings listed above.

NOTE: The LV2 Double Pole heating only model may also be used in Single Pole applications, however only the LINE 1 and LOAD 1 terminals must be

used.  Only the LINE 1 and LOAD 1 terminals are switched during normal temperature cycling.

All wiring performed must comply with applicable codes and ordinances to your local area.

LOCATION:

The thermostat should be mounted in a standard 2 inch X 3 Inch Electrical Outlet Box.  For Ease of installation, use a “deep” style box to assist in allowing room for

the excess wires.  A mounting location should be chosen where it will be constantly exposed to the average room temperature.  The thermostat should also be located
away from the following: concealed hot or cold water pipes, air ducts, hallway drafts, fireplaces, or stairways, to be able to sense temperature and control your heating

or cooling equipment properly.  For the heating only models, avoid positioning this thermostat in a location which is directly above any baseboard heating components,

as this will cause erratic temperature control.

INSTALLATION:

[1] Disconnect the supply power before removing your old thermostat (if applicable) and keep it off until after you have completed installing this thermostat. Double

check that the thermostat is rated for the voltage and amperage to be switched.  [2] If replacing an old thermostat, remove it carefully to avoid damaging the wires or

their insulation.  Check the existing wire insulation for cracks, nicks, or fraying and apply certified electrical tape where necessary to achieve adequate insulation, or

replace the wires in an approved fashion.  [3] For all three heating or cooling models, turn the dial fully counter-clockwise prior to installing.  [4] Use the diagrams

shown above as a guide to ensure a proper connection between your voltage supply and your heating or cooling components, using the appropriate LINE and LOAD

designations.  [5] Attach the connection wires using appropriately sized solderless wire connectors (provided).  Be sure that ALL wire connections are securely

tightened.  [6] Ensure that the thermostat is appropriately connected to the ground wire at the grounding screw on the rear of the thermostat housing.  [7] Carefully

bend all of the solid conductors and push the excess wire length to the rear of the electrical box to allow enough room for the rear portion of the thermostat to be

recessed into the box.  Be sure that no portions of the exposed ground wire are allowed to accidentally come in contact with the LINE or LOAD terminals on the rear of

the thermostat.  [8] Carefully push the thermostat all the way into the box opening, and mount the thermostat to the box using appropriately sized mounting screws.

Ensure that the mounting screws will not project too far into the box and come in contact with any of the wires causing a short circuit.  [9] Once complete, turn the

power back on to your heating or cooling equipment and turn dial to the desired temperature setting.

• Both poles are
only broken when
the dial is in the
OFF position

52013