Intermatic T7401B Owner's Manual

Intermatic Misc Electronics Owner's Manual - T7401B.
Download
Page  of 1
4.8, 1244 votes
background image

MODEL: T7401B

SEVEN-DAY DIAL TIME SWITCH

4 POLE SINGLE THROW

MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS

CONTACT RATINGS:

40 AMP. RESISTIVE EACH POLE 120V -480V AC.

40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR

277V AC.  1000 VA PILOT DUTY EACH POLE 120V - 277V AC.

24 FLA,  144 LRA  (2 HP) - 120V AC.;  28 FLA,  168 LRA  (5 HP) - 240V AC.

     SINGLE PHASE

28 FLA, 168 LRA (7 1/2 HP) -208V AC.,  (10 HP) -240V AC. 3 PHASE

CLOCK MOTOR: 125 VOLTS - 60 HZ.

FOR REPLACEMENT MOTOR, ORDER WG1600 

WIRING INSTRUCTIONS

This  Time  Switch  can  be  wired  to  control  one  to  four  circuits  simultaneously  on  a  seven

day  schedule.  Clock  motor  voltage  may  be  other  than  load  voltage,  but    must  be  as 

specified.  For  terminal  markings,  internal  wiring  and  contact  arrangements  refer  to  wiring 

diagram above.  Use solid or stranded COPPER 

only  wire with insulation to suit installation. 

See table for gauge selection. To make power connections remove 1/2 inch of insulation from 

wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger 

screw driver to tighten terminal screws firmly. 

 REPLACE FRONT INSULATOR BEFORE 

TURNING ON ELECTRICITY.

PROGRAMMING INSTRUCTIONS

1.

  TO    SET  “ON”  TIMES,  place  bright  ON  trippers  against  edge  of  CLOCK-DIAL  at

  day-of-week  and  time-of-day  when 

“ON”  operations  are  desired.  Tighten  tripper

  screws securely.

2. 

TO  SET  “OFF”  TIMES,  place  dark  OFF  trippers  against  edge  of  CLOCK-DIAL  at

  times when 

“OFF” operations are desired. Tighten tripper screws securely.

3. 

TO  SKIP  DAYS,  omit  trippers  for  the  day(s)    automatic  operations  is/are  not  required. 

4.

  TO  SET  DIAL  TO  TIME-OF-DAY,  turn  dial  CLOCKWISE  and  align  the  exact  day-of-

  week  and  time-of-day  (AM  or  PM)  on  dial  with  the 

TIME  POINTER.  Some  allowance

  may be required to compensate for gear backlash.

  CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.

OPERATING INSTRUCTIONS

• TO OPERATE SWITCH MANUALLY:  Move  MANUAL  LEVER  below  CLOCK-DIAL

  left or right as indicated by arrows. This will not affect next automatic operation.

• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME:  Reset  time-of-

  day, see step 4 of programming instructions.

  DISCONNECT ELECTRICITY BEFORE ANY BEHIND-THE-INSULATOR WORK.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158TS10978

120 V

60 HZ

TO

LOADS

SUPPLY

WIRING DIAGRAM

GROUND

SCREW

PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE

INSULATION CLEARS

PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14

12

10

8

15

20

30

40

60

60

60

75

1/2

1

2

-

2

2 1/2

3

5

3

4

5

7 1/2

3

5

7 1/2

10

CLOCK

MOTOR

2

1

A

3 4

5 6

7 8

B

LR3730