MODEL:  

T2006

CALENDAR DIAL TIME SWITCH

FOR UP TO 42 TIMING OPERATIONS ON 7 DAY SCHEDULE 

SINGLE POLE DOUBLE POLE

SWITCH RATING:  20 AMP. 125-480 VOLTS A.C. 

1/2 HP-125V  1 HP-250V.

CLOCK MOTOR: 208-277V. - 60 HZ.

MINIMUM ON OR OFF TIME IS 2 HOURS.
EXTENDABLE IN 2 HOUR INCREMENTS;

WIRING INSTRUCTIONS

This  Time  Switch  can  be  wired  to  control  two  circuits  as  Single  Pole 

Double throw, or to control one circuit as Single Pole Single Throw. Either  

normally open (NO) or normally closed (NC). 
PROGRAMMING INSTRUCTIONS

                 

TO PROGRAM TIME SWITCH, Depress tripper(s) into dial at desired 

time(s) operation(s) is/are required.

• ON TIME: First tripper turns on the load for 135-145 minutes. Each  

additional tripper will lengthen the on time by 2 hours.

  OFF  TIME:  First  tripper  in  raised  position  turns  off  the  load  for 

95-105  minutes.Each  additional  space  will  lengthen  the  of  time  by 

2 hours.
SET  TIME-OF-DAY:  Turn  dial  in  clockwise  direction  only  and  align 

the exact day -of-week and time-of-day on dial (the time when switch 

is being put in operation) to the “TIME” indicator.

 

 

TIME

DIAL

INSULATOR

MANUAL

LEVER

CAP
NUTS

CLOCK

MOTOR

SUPPLY

NORMALLY  CLOSED  CIRCUIT

NORMALLY  OPEN CIRCUIT

                              FIG. 1                                                               WIRING DIAGRAM

CLOCK

COM.

N.C.

N.O.

N.C.

LOAD

NO.

LOAD

1.

2.

OPERATING INSTRUCTIONS

TO  CONTROL  LOADS  MANUALLY,  Move  manual  lever  (See  Figure 

1)  up.  This  lever  will  close  normally  open  circuit  and  open  the  normally 

closed  circuit.  To  return,  to  automatic  control,  move  lever  back  to  its 

original position .

TO REMOVE MECHANISM FROM CASE, disconnect electricity and all 

wiring. Depress retainer spring at upper left, or unscrew mounting screws, 

then grasp dial and pull mechanism out.

IN CASE OF POWER FAILURE, or retard/advance time reset dial. See 

step (2) of programming instructions.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158TS11743

LR3730