Intermatic T103R Owner's Manual

Intermatic Misc Electronics Owner's Manual - T103R.
Download
Page  of 1
4.8, 1165 votes
background image

MODEL: T103R

24 HOUR DIAL TIME SWITCH (DPST)

IN TYPE 3R DUSTPROOF RAINPROOF ENCLOSURE, SUITABLE FOR POOL
EQUIPMENT CONTROL IF INSTALLED 5 FT.  OR MORE FROM EDGE OF POOL.

40 AMP. RESISTIVE, INDUCTIVE  TUNGSTEN OR

1000V.A. PILOT DUTY 120/208/240 VOLT AC;

2 H.P. (24 FLA) - 120 V. AC; 5 H.P. (28 FLA) - 240V. AC

CLOCK MOTOR: 110-125V. 60 HZ.

 

WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid or strand 

COPPER only wire with insulation to suit installation. See gauge selection table for 

normal service applications. To make power connections remove 1/2 inch of insula-

tion from wire ends. Insert bare ends of wire under the pressure plate of terminals. 

Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum). 

REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.

PROGRAMMING INSTRUCTIONS

•TO SET “ON” AND “OFF” TIMES: Hold  trippers

  against  edge  of 

CLOCK-DIAL,  pointing  to  time  (AM  or

  PM)  when 

ON  and  OFF  operations  are  desired, 

  tighten  tripper  screws  firmly.  For  additional  tripper  pairs

  on 

CLOCK-DIAL order 156T1978A.

•TO SET TIME-OF-DAY:  Pull  CLOCK-DIAL  outward.

  Turn  in  either  direction  and  align  the  exact  time-of-day

  on the 

CLOCK-DIAL (time now, when switch is put into

  operation)  to 

TIME  POINTER.  DO  NOT  MOVE

  POINTER.

OPERATING INSTRUCTIONS

•TO OPERATE SWITCH MANUALLY:  Move  MANUAL

  LEVER below CLOCK-DIAL left or right as indicated by

  arrows. This will not effect next operation.

•INCASEOFPOWERFAILURE, reset CLOCK-DIAL to

  proper time-of-day. See programming instructions.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

154--01002   

 

 

 

CLOCK  MOTOR  VOLTAGE  AND  CYCLE  MUST  BE  AS  SPECIFIED.  TO 

ORDER  REPLACEMENT,  INDICATE  PART  NO.  (WG--)  ON  MOTOR  COVER.

CLOCK

DIAL

TIME

POINTER

OFF 

TRIPPER

MANUAL 

LEVER

ON

TRIPPER

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP (°C)

75° INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

 120V        240V

14

12

10

8

15

20

30

40

60

60

60

75

1/2

1

2

2

2 1/2

3

5

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE WIRE

INSULATION CLEARS 

PRESSURE  PLATE

          

3 PHASE

 240V       240V

N/A

N/A

FIGURE 1

LR3730

CLOCK

MOTOR

TYPICAL

WIRING

DIAGRAM

120/240

VOLT

3 WIRE

SUPPLY

TO

LOADS

GROUND

LINE  2

LINE 1

A

4

2

GR.

3

1

NEUT.