30" to 36" 

(76.2 cm to 91.4 cm)

bottom of canopy to

cooking surface

vent and power

supply cable entry

location

16" 

(40.6 cm)

min.

7" 

(17.8 cm)

7" 

(17.8 cm)

side

cabinet

side

cabinet

7" (17.8 cm) max.

2" (50.1 mm) 

min.

30" (76.2 cm)

minimum

centerline

Installation Clearances

Venting Requirements

■ Vent system must terminate to the outside.
■ Do not terminate the vent system in an attic or other enclosed

area.

■ Do not use 4" (10.2 cm) laundry-type wall caps.
■ Use metal vent only. Rigid metal vent is recommended. Do

not use plastic or metal foil vent.

For the most efficient and quiet operation:
■ Use a straight run or as few elbows as possible.
■ Use no more than three 90° elbows.
■ Make sure there is a minimum of 24" (61 cm) of straight vent

between the elbows if more than one elbow is used.

■ Do not install two elbows together.
■ Use duct tape to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around 

the cap.

Cold weather installations

An additional backdraft damper should be installed to minimize
backward cold air flow and a nonmetallic thermal break to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.  

The break should be as close as possible to where the vent
system enters the heated portion of the house.

Make-up air

Local building codes may require the use of make-up air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in 
your area.

Venting methods

This canopy hood is factory set for venting through the roof 
or wall. 

A 6" (15.2 cm) round vent system is needed for installation (not
included). The hood exhaust opening is 6" (15.2 cm) round.

NOTE: Flexible vent is not recommended. Flexible vent creates
back pressure and air turbulence that greatly reduces
performance.

Vent system can terminate either through the roof or wall. To vent
through a wall, a 90° elbow is needed.

For non-vented (recirculating) installations see “Non-Vented
(Recirculating) Installations” in “Install Vent” section.

Calculating Vent System Length

To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.

Maximum equivalent vent length is 35 feet (10.7 meters).

Roof venting

roof cap

wall
cap

6" 

(15.2 cm)

round vent

Wall venting

Non-vented

(recirculating)

6" 

(15.2 cm)

round vent

deflector

90° elbow

wall cap

1 — 90° elbow 

5 ft.  (1.5 m)

8 ft. (2.4 m) straight 

8 ft.  (2.4 m)

1 — wall cap 

0 ft.

(0 m)

system length

=

13 ft. (3.9 m)

6 ft. (1.8 m)

2 ft.

(0.6 m)

Example vent

system

Vent piece 

6" (15.2 cm) round

45° elbow

2.5 feet

(0.8 m)

90° elbow

5.0 feet

(1.5 m)