Cooling system  61 

 
Feature 

Specification 

Facility input temperature to the HP POD 

20c 

12º to 24ºC (55º to 75ºF) 

Max design pressure 

1,034 kPa (150 psi) 

HP POD 20c pressure drop 

172.4 kPa (25 psi) 

HP POD 20c water flow rate 

454 lpm (120 gpm*) 

Chil ed water supply and return 

connections 

Two DIN PN16 DN80 flanges 

 

*Measurement is in US gal ons per minute. 

 

Cooling system components 

Each of the three heat exchanger area access hatches are rated NEMA 3R for outdoor use. The exterior of 

the hatches are coated with a durable finish to protect against corrosion. The access hatches are located on 
the roof of the POD. The heat exchangers can be accessed from the roof of the POD by removing one of the 

six access hatches. 
Top view shown 

 

 
Item 

Component 

Description 

Heat exchangers 

Uses chilled facility water to cool the air in the HP POD 20c 

Chilled water supply 

header 

Provides cooled chilled water from the site chilled water system to the heat 

exchangers 

Chilled water return 

header 

Provides heated chil ed water to the return site chil ed water system 

 