HP Performance Optimized Data Center (POD) 20cp User's Manual | Page 18
Life safety systems 18
Life safety systems
Life safety overview
The HP POD 20c has multiple life safety systems that work together to protect the HP POD 20c equipment and
personnel. The following life safety systems are available on the HP POD 20c:
•
EPO system (on page 18)
•
VESDA air sampling smoke detection system (on page 21)
•
(Optional) fire protection system (on page 21)
•
Emergency egress (on page 24)
•
ECS connection to customer emergency systems
EPO system
If the HP POD 20c must be shut down during an emergency, the EPO system automatical y shuts off al power
to the HP POD 20c and activates the EPO indicator on the ECS panel door and the EPO strobe on the POD
interior.
To ensure that all rack-mounted UPS devices are shut down during an EPO event, verify that each
rack-mounted UPS device is connected to the HP POD 20c EPO system.
The EPO system can be activated two ways:
•
Excessive high temperature in the hot aisle—The HP POD 20c includes two EPO temperature sensors.
If both sensors reach 60°C (140°F), an EPO shutdown is triggered automatical y. Both sensors are
located in zone 2.
•
Manual initiation—To manual y trigger an EPO shutdown, press either of the EPO buttons. One EPO
button is located on the POD interior near the main exit, and an optional second EPO button is located
on the POD exterior.
Also See for HP Performance Optimized Data Center (POD) 20cp
- HP Performance Optimized Data Center (POD) 20cp Getting Started Guide 38 pages
- HP Performance Optimized Data Center (POD) 20cp Reference Guide 37 pages
- HP Performance Optimized Data Center (POD) 20cp Setup and Install 22 pages
- HP Performance Optimized Data Center (POD) 20cp Service and Maintain 81 pages
Related Manuals for HP Performance Optimized Data Center (POD) 20cp
-
HP Data Center Solutions Data Center Environmental Edge User's Manual
113 pages
-
HP Data Center Solutions Performance Optimized Data Center (POD) 240a User's Manual
93 pages
-
HP Data Center Solutions Performance Optimized Data Center (POD) 40c User's Manual
84 pages
-
HP Data Center Solutions Performance Optimized Data Center (POD) 40cp User's Manual
63 pages