HP Performance Optimized Data Center (POD) 20cp Setup and Install | Page 16

HP Data Center Solutions Setup and Install - Performance Optimized Data Center (POD) 20cp.
Download
Page  of 22
4.6, 1230 votes
background image

 

Water quality requirements  16 

Piping materials 

Do not use the following interconnecting piping materials in a closed water system: 
•  Oxidizing biocides 
•  Aluminum components 
•  Brass components with high levels of zinc 
•  Non-stainless steel iron components 

 

Water precautions 

Take the following precautions before installation of the HP POD: 
•  Verify that all foreign matter and particulates are flushed from the system. Water might be discolored 

during the initial flushing of the system. Clear running water is the sign that all foreign matter and 
particulates have been flushed from the system. 

•  Evaluate the short-term and long-term system requirements against the available water capacity. 
•  Ensure that the chilled water loop is properly designed for liquid cooling systems and is separate 

from the sanitary water systems in your building (bathroom, sink, drinking water). 

•  Ensure facility managers are aware of the additional load being added to the chil ed water supply of 

the building. Be aware that the added heat load might affect other components being cooled by the 
chil ed water plant. 

 

Condensation management 

  

 

CAUTION:  During operation, avoid leaving the HP POD doors open, to maintain accurate 
environmental conditions inside the HP POD. 

  

Supply cooling water that is above the dew point inside the HP POD to prevent condensation forming on 
the heat exchangers. 
The heat exchanger drip tray will collect any condensation that forms on the heat exchangers. This 
col ected condensate drains out of the HP POD through the heat exchanger condensate drains. HP 
recommends connecting condensate drains on the HP POD to a facility drain to prevent col ection of 
water near the HP POD. 
There is one heat exchanger condensate drain outlet located near the bottom of the HP POD in between 
the access doors on the hot aisle side. There are three drains for the water main supply and return lines 
located near the bottom of the HP POD on the cold aisle side. 
To avoid excessive buildup of condensate and to conserve energy, raise the cooling water temperature to 
above the dew point to manage condensation while maintaining the necessary cooling capacity. 