HP Performance Optimized Data Center (POD) 20cp Service and Maintain | Page 74

HP Data Center Solutions Service and Maintain - Performance Optimized Data Center (POD) 20cp.
Download
Page  of 81
4.1, 2417 votes
background image

 

Regulatory information  74 

  The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an 

existing facility, and are not suitable as "service entrance" for connection to the utility. 

  The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, 

in restricted access locations, with field wiring terminals provided for permanent supply connections. 

  The HP POD 20c meets the following ratings. 

 
Feature 

Specification 

Category 

Rated Overvoltage Category II  

Protection 

Surge protection device 

Class 

Class1 

Ambient temperature 

2°C to 54°C (35.6°F to 129.2°F) 

Relative humidity 

0% to 100% humidity 

 

  As part of the overall certification, relevant sections of the International Building Code have been 

applied as part of the design and evaluation. The current design supports wind loads up to 90 mph. 

 

Regulatory requirements for EXIT signs 

Manufacturers of tritium EXIT signs are “specific licensees,” meaning they are licensed by the NRC or an 
Agreement State. The signs are considered “general y licensed devices,” because they are inherently safe 

enough to be handled or used by anyone with no radiation training or experience. Although purchasers – 

known as “general licensees” – do not need authorization from the NRC or a state regulatory agency to 

possess the signs, they are subject to certain regulatory requirements regarding handling, transfer or disposal 
of the signs. For more information, see the NRC website 

(http://www.nrc.gov/reading-rm/doc-collections/fact-sheets/fs-tritium.html#_edn2). They are also subject 

to NRC or Agreement State inspection and enforcement action (including fines) for violating those 

requirements. Manufacturers must inform purchasers of the EXIT signs of the regulatory requirements for 

general y licensed devices. The general licensee is required to designate an individual responsible for 
complying with the regulatory requirements. 
Under NRC regulations, a general licensee using tritium EXIT signs: 

  must NOT remove the labeling or radioactive symbol, or abandon a sign;  

  must properly dispose of an unused sign (see below);  

  must report to the NRC or the appropriate Agreement State any lost, stolen or broken signs;  

  must inform the NRC or an Agreement State of a name change, change of address or replacement of 

a general licensee’s designated representative;   

  must NOT give away or sel  the sign to another individual, company or institution unless the device is 

to remain in use at its original intended location; in such a case, the transferor is to notify the recipient 

of the regulatory requirements and must notify the NRC or Agreement State of the transfer within 30 
days.  

Tritium EXIT signs must NOT be disposed of as normal trash. To dispose of a sign properly, a general licensee 

must transfer the sign to a specific licensee. This would typically be a manufacturer, distributor, licensed 

radioactive waste broker, or a licensed low-level radioactive waste disposal facility. These facilities may 
charge a fee for this service. 
Within 30 days of disposing of a sign, the general licensee is required to file a report to the NRC or 

Agreement State that includes: 