Periodic maintenance  64 

Component to be inspected 

Task 

Frequency 

Capable Party 

Humidifier drains 

Put the humidifier in system flush 

mode and inspect drain flow and 
water supply flow. Inspect, clean, 

and/or replace as necessary. 

Quarterly 

Qualified personnel 

— 

Inspect for any internal or external 

water leaks, repair or replace 

leaking components. 

Quarterly 

Qualified personnel 

— 

Using LLS, verify proper cylinder 
operation. Inspect the cylinder for 

blackened areas and, if present, 

check the condition of the 

electrodes. If necessary, replace 
the cylinder. 

Quarterly 

Qualified personnel 

— 

Replace the cylinder. 

Annual y 

Qualified personnel 

 

 

ECS 

 
Component to be inspected 

Task 

Frequency 

Capable Party 

Ful  system functional check 

Operational check of al  system 

components 

Quarterly 

Qualified personnel 

— 

Check and clear alarm log 

Quarterly 

Qualified personnel 

— 

Inspect and test ECS bat ery 
backup system 

Every 2 years 

Qualified personnel 

 

 

Electrical 

Maintenance of the electrical components might require the following: 

  Expose personnel to high voltage. 

  Allow personnel to come into direct contact with high voltage. 

  Power down the POD during the execution of the maintenance item. 

You must explicitly state and acknowledge if a POD power down will be possible. If a power down is not 

possible, LLS inspections will be conducted and further action will be taken at your discretion. 

 
Component to be inspected 

Task 

Frequency 

Capable Party 

Electrical connections 

Use LLS to check for major 

electrical connections (torque 
marks, sizzle, and acrid odor): 

  Main/House Power Feeds 

  Busway End Feeds, Drop 

Boxes (including cables and 
cord caps) 

  Electrical panels, breakers, 

and disconnects 

  480/415 VAC transformer 

Quarterly 

Licensed electrician 