Periodic maintenance  63 

 

CAUTION:   If a serious leak develops, shut down the POD immediately and isolate the chilled 

water cooling system from the site. Contact HP immediately to initiate a field service cal . Do not 

attempt to repair the chil ed water cooling system. At empting to self-repair the chil ed water 
cooling system during the warranty or service contract period shifts all liability to you. 

  

  

 

IMPORTANT:  Power down the POD after a leak is detected. 

  

Non-isolable leak detection 
A non-isolable leak is a leak from the main supply line or the return header. 
To repair a non-isolable leak: 
1.  Power down all IT equipment. 
2.  Re-direct the leaking water away from the IT equipment. 
3.  Repair the leak or contact HP if you are stil  within your service contract. 
Isolable leak detection 
An isolable leak is any type of leak that does not occur from the main supply line or the return header. 
To repair an isolable leak: 
1.  Inspect the zone indicated on the ECS Status Overview screen. You might need to inspect each zone 

condensate drain pan to determine the exact location of the leak. 

2.  Power down the IT equipment in the zone where the leak is located. 
3.  Determine the affected heat exchanger. 
4.  Close and danger tag the supply and return valves to the affected heat exchanger. 

If the heat affected exchanger cannot be identified, close al  the heat exchanger supply and return 
valves in the affected zone and open one supply valve at a time to determine the location of the leak. 

5.  Repair the leak or contact HP if you are stil  within your service contract. 

 

Humidifier (if installed) 

 
Component to be inspected 

Task 

Frequency 

Capable Party 

Humidifier 

  Inspect for water leaks, verify 

that no sparks form between 

the electrodes during 
operation 

  Inspect the general operation 

of the cylinder. 

  Bi-weekly, if 

staffed 

  Quarterly, if 

not staffed 

Qualified personnel 

Humidifier drains 

Verify the following: 

  Drains are in working order 

  There is an air gap at the 

funnel/drain entry into the site 

system 

  Drain discharge is not getting 

water on external equipment 
or grounding system 

Quarterly 

Qualified personnel 