HP Performance Optimized Data Center (POD) 20cp Service and Maintain | Page 44

HP Data Center Solutions Service and Maintain - Performance Optimized Data Center (POD) 20cp.
Download
Page  of 81
4.1, 2417 votes
background image

 

Removal and replacement procedures  44 

4.  Replace the cold-aisle temperature sensor cover (1). 
5.  Replace the four screws that secure the cold aisle temperature sensor cover (2). 

 

 

Temperature sensors (hot aisle) 

The HP POD 20c contains three temperature sensors in the hot-aisle. 

 

You need a screwdriver to remove and replace the hot aisle temperature sensors. 

 

Removing the hot aisle temperature sensor 

1.  Remove the four screws (1) that secure the hot-aisle temperature sensor cover, and then remove the 

cover (2). 

2.  Label the hot-aisle temperature sensor wires or take a picture to remember which wires to reconnect 

later. 

3.  Disconnect the wires. 

0.465818s