Removal and replacement procedures  40 

4.  Rotate the immersion sleeve counterclockwise (1), and then pul  forward to remove the entire sensor 

from the chilled water header (2). 

 

 

Replacing the temperature sensor in the chilled water system 

1.  Insert the new sensor probe into the chil ed water header (1). 
2.  Rotate the immersion sleeve clockwise to secure the sensor onto the header (2). 
3.  Reconnect the wiring, replace the sensor cover, and replace the removed insulation. 

 

 

Chilled water temperature sensor internal components 

The HP POD 20c contains two chilled water header temperature sensors. One is located in the chilled water 

supply header and one is located in the chil ed water return header. 
You need a screwdriver to remove and replace the chil ed water temperature sensor internal components. 

 