Removal and replacement procedures  26 

The Rittal SK 3326 ventilation fan has been discontinued, so if it malfunctions, you must order the Rit al SK 

3243 ventilation fan. 
To instal  the new fan, see the instal ation instructions included with the fan. 

 

Filters 
Heat exchanger air filters 

There are two heat exchanger air filters per cooling zone for a total of six filters. 

 

You do not need any tools to remove or replace the heat exchanger air filter. 

 

Removing the heat exchanger air filter 

1.  Pull the locking tabs away from the filter to release it. 
2.  Pul  the filter down through the frame channels to remove it. 

 

 

Replacing the heat exchanger air filter 

1.  Angle the filter to position the top corners in the frame channels, and then push the filter up to the top of 

the frame. 