Illustrated parts catalog  10 

HP POD 20c racks 

The HP POD 20c contains a total of ten IT racks. 

  

 

CAUTION:   If any racks contain empty RU space, use the HP POD 20c fil er panels to maintain 
the efficiency of the HP POD 20c thermal system. Filler panels are available from HP in 10-pack 

quantities (part number AQ682A) and 100-pack quantities (part number AS993A). 

  

For more information about racks and network cabling, see the HP Performance Optimized Datacenter 

Networking Guide

 

Aisle clearances 
Cold aisle clearance 

The maximum protrusion of any installed IT component directly impacts the available cold aisle clearance for 
removal and replacement of other IT components. Maximum component depth must fol ow the clear aisle 

distance calculations. The following figure shows how to calculate this distance. 

 

The maximum rack face-to-cold aisle wal  distance is 39.5 inches. In the figure, X represents any protrusion 

into the cold aisle starting from the rack face of the instal ed IT component (for example, the bezel). Y 
represents cold aisle clearance. The cold aisle clearance dictates the maximum depth (D) of any instal ed IT 

component. To find the maximum cold aisle clearance, calculate 100.33 cm (39.5 in) - X = Y. 

  

 

IMPORTANT:  As the value for X increases, the value for Y decreases, which also decreases the 
maximum depth allowed for an installed component. 

  

 