HP POD 20c capacities  7 

HP POD 20c capacities 

HP POD 20c capacity limitations 

The capacity limitations for the HP POD 20c are separated into two categories: electrical power and 
mechanical cooling capacities. Both of these categories are interdependent and must be considered in 

conjunction with the overal  customer requirements. 

 

Electrical power capacities (critical IT power) 

The electrical system of the HP POD 20c contains two main feeds, A and B, that are each rated at 400 A 480 

V Delta 3-wire. The HP POD 20c has two critical IT load circuits that are each rated at 200 A, which 

electrical y limits the POD regardless of the redundancy configuration. 

 

Mechanical cooling capacities 

The HP POD 20c cooling system consists of 3 zones. Each zone includes 2 heat exchangers and 12 fans. 

Cooling capacities are based on: 

  Chilled water inlet temperature of 15.6ºC (60ºF) 

  Pure water cooling 

  Chilled water flow rate of 454 lpm (120 gpm) 

  Average air flow of 1200 cfm per rack 

 

Overall system capacities 

The HP POD 20c overall system capacities are provided in the fol owing table. The customer must understand 

the level of redundancy that is required for the application and its associated limiting factor. 

  
Redundancy level 

Electrical (kW) 

Thermal (kW) 

Limiting factor 

288 

300 

Electrical 

2N 

144 

150 

Electrical 

 

For more information on the electrical limitation factors, see "Electrical power capacities (critical IT power) 
(on page 7)." 