Site requirements  14 

 
Feature 

Specification 

Facility input temperature to the HP POD 

20c 

12º to 24ºC (55º to 75ºF) 

Max design pressure 

1,034 kPa (150 psi) 

HP POD 20c pressure drop 

172.4 kPa (25 psi) 

HP POD 20c water flow rate 

454 lpm (120 gpm*) 

Chil ed water supply and return 

connections 

Two 7.62 cm (3 in) ASME B16.5 

class #150 flanges 

 

*Measurement is in US gal ons per minute. 

 

Piping materials 

Do not use the following interconnecting piping materials in a closed water system: 

  Oxidizing biocides 

  Aluminum components 

  Brass components with high levels of zinc 

  Non-stainless steel iron components 

  PVC 

  

 

IMPORTANT:  Even though some PVC grade piping materials are designed to handle the 
expected water pressure, the use of PVC materials should be reviewed and approved by the 

customer site engineers. 

  

 

Power infrastructure installation 

When determining the final location of the power connections, consider the fol owing: 

  Distance between the facility utilities and the location of the HP POD 20c 

  Distance between possible UPS or generator locations and the HP POD 20c 

  Requirements for routing electrical feeders (underground or overhead) 

The facility power connection must be installed in compliance with local electrical codes and regulations. HP 
reference electrical installation design is based on a maximum distance of 15.2 m (50 ft) or a line of sight 

between the disconnect and the HP POD 20c. 

 

Site electrical system 

To ensure a complete and safe integration of the HP POD solution with your facility, HP requires that you 

complete the following actions for the installed electrical system prior to the instal ation of the HP POD 

solution: 

  Short circuit analysis 

  Arc flash study 

  Circuit breaker coordination study 