HP Performance Optimized Data Center (POD) 20cp Reference Guide | Page 13

HP Data Center Solutions Reference Guide - Performance Optimized Data Center (POD) 20cp.
Download
Page  of 37
4.2, 1322 votes
background image

 

Site requirements  13 

Requirement 

Location 

Specification 

Humidifier drain 

Cold aisle side (1) 

3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 

 

 

Chilled water supply 

The fol owing are the water quality requirements and specifications: 

  Closed-loop water must not contain any lime scale deposits or loose debris. 

  The temperature of the chilled water supplied to the HP POD 20c must be 12ºC to 24ºC (55ºF to 75ºF). 

  

 

CAUTION:   Freezing water can cause a blockage and damage to the unit. In outside locations 

that are subject to freezing temperatures, an additive such as glycol might be necessary to lower 

the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP 
POD 20c must be de-rated accordingly. 

  

  

 

IMPORTANT:  The chil ed water system piping and heat exchangers must be drained completely, 
and then purged using compressed air when storing or transporting at or below freezing 

temperatures. 

  

  

 

IMPORTANT:  Operating the chil ed water system at the higher end of the acceptable range 
decreases the overall thermal capacity of the POD. 

  

Acceptable water quality specifications 
Water must be maintained per the fol owing acceptable water quality standards. 

 
Parameter 

Range 

pH 

8.0–10 

Specific conductance at 25ºC (77ºF)  10–2500 µmhos 
Alkalinity ("M" as CaCO3) 

150–1000 ppm 

Sulfur (SO4) 

0–150 ppm 

Chloride (Cl) 

0–100 ppm 

Hardness (CaCO3) 

0–350 ppm 

Calcium hardness (CaCO3) 

0–200 ppm 

Magnesium hardness (CaCO3) 

0–150 ppm 

Copper (Cu) 

< 0.20 ppm 

Iron (Fe) 

< 3.0 ppm 

Aluminum (Al) 

< 0.50 ppm 

Sodium (Na) 

0–1000 ppm 

Silica (SiO2) 

0–150 ppm 

Zinc (Zn) 

< 1.0 ppm 

Manganese (Mn) 

< 0.1 ppm 

Phosphate Ortho- (PO4)  

< 3 ppm 

Bacteria 

< 1000 CFU/ml 

Suspended solids 

< 10 ppm 

 

If your water is out of range, consult a water quality expert. 
The fol owing table describes the chil ed water system specifications for the HP POD 20c. 