HP Performance Optimized Data Center (POD) 20cp Getting Started Guide | Page 24
Site plan requirements and actions 24
• Assembly equipment locations
Item
Description
1
Crane
2
Reach
3
Truck
4
Area clear for scissors lift and forklift
HP POD 20c lifting requirements
WARNING: The only approved method for lifting the HP POD 20c is the use of a spreader bar
harness. Lifting an HP POD 20c in any other manner can cause damage to the HP POD 20c and
void your warranty. The harness and lifting connections must be perpendicular to the lifting
blocks.
HP POD 20c storage requirements
If the site is not ready for assembly and operation, determine a location for storage when creating the site
plan.
CAUTION: The HP POD 20c must maintain 20% relative humidity to minimize condensation and
oxidation within the HP POD 20c.
CAUTION: While being stored, the HP POD 20c must be kept in a level position even if stored
on a trailer.
Changes in ambient temperatures can cause condensation in a non-operational HP POD 20c. If the HP POD
20c is placed in storage or is in non-operating mode for over 72 hours, HP recommends using one of the
fol owing methods to minimize condensation and oxidation within the HP POD 20c:
• Desiccant unit
• Desiccant material
• Heater with a fan
• Air conditioner with a heater strip
Consult with HP Services to determine the most effective method.