HP Performance Optimized Data Center (POD) 20cp Getting Started Guide | Page 12

HP Data Center Solutions Getting Started Guide - Performance Optimized Data Center (POD) 20cp.
Download
Page  of 38
4.9, 1392 votes
background image

 

Site requirements  12 

Front view shown 

 

 

Utilities 

Consider the proximity to required utilities, such as power, water, and network connections. While the 
required utilities can be brought to nearly any selected site, there is the potential for increased costs and 
decreased efficiency when the HP POD 20c is located farther from the utility sources. 
For utility clearance information, see "Dimensions and clearances (on page 8).

 

Humidifier water supply 

The HP POD 20c requires supply water for the humidifier. The supply water must meet the fol owing 
requirements. 

 
Requirement   

Specification 

Pressure 

Between 20 and 110 psi, 0.1 and 0.8 MPa 

Temperature 

Between 1º and 40°C (33º and 104°F) 

Minimum flow rate 

1.45 lpm (0.12 gpm) 

Connection 

1.9 cm (.75 in) G 

Adapter to 1.9 cm (.75 in) FPS 

Hardness 

No greater than 40°fH (equal to 400 ppm of CaCO3) 

Conductivity 

100 to 1250 μS/cm 

Organic compounds 

None 

Type of water 

Drinking water. Do not use de-mineralized or softened water. 

Instant water fill flow 
rate 

0.6 lpm (0.16 gpm) 

Humidifier 

For the exact requirements, see the humidifier documentation. 

   

 

IMPORTANT:  If your water is out of range, consult a water quality expert. 

In addition to the previous requirements, observe the fol owing requirements and recommendations: 