Honeywell Honeywell Thermostat V8043F User's Manual

Honeywell Thermostats User's Manual - Honeywell Thermostat V8043F.
Download
Page  of 5
4.1, 1474 votes
background image

2004.09   Printed in Canada

Form No. 95C-10932

APPLICATION

   These valves consist of a motorized
actuator  and valve assembly for controlling
the flow of hot water to a heat exchanger
such as a radiator, convector, finned
baseboard radiator, or infloor radiant coil
for space temperature control. The V8043
5000 series valves provide two-position,
straight through control of supply water at
up to 300 psi operating pressure.
   Quick Fit actuator provides easy snap on and
off connection to the valve assembly.

SPECIFICATION

Actuator Electrical Rating:

24Vac 60 Hz, 0.30 A Current Draw,
5 W, 7.2 VA  maximum

Electrical Connection:

18” leads or screw terminal board

Auxiliary Switch Rating:

120V, 4.4A running, 26.4A Inrush (60 Hz);
50 VA Pilot duty at 24 V.

Fluid Temperature:

Standard models (class F motor):
200

° F (93° C) Max.

Ambient Temperature:

125

°F (52° C) Max.

Humidity Limits:

95% Relative Humidity, Non-condensing

Shipping and Storage Temperature:

-40

°F to 150°F (-40°C to 65°C).

Atmosphere:

Non-corrosive, non explosive.

Maximum Soldering Temperature:

500

°F (260°C). Rubber ball plug must be

moved away from the seat for soldering.

Maximum System Pressure Rating:

300 psi (2000 kPa), PN20.

Flow Characteristics:

Quick opening for on-off application.
Slow return for water hammer resist.

Maximum Close-off Rating (@ Flow
Capacity Rating) :

20 psi (@ 3.5 Cv)
8 psi (@ 8 Cv)

Actuator Materials:

Case:galvanized steel.
Cover : zinc plated steel.
Sector gear: Brass

Valve Material:

Body of forged brass; drive shaft stem of
stainless steel; ball plug of Buna-N rubber;
o-ring seals of EPDM rubber.

Service Medium:

   Suitable for glycol/water mix up to 50:50
use in closed hydronic systems. Not for
use with oxygenated water, potable water
or steam.
   Use this valve in hydronic systems which
do not contain dissolved oxygen in the
system water. The dissolved oxygen,
which is found in systems that have a
frequent source of make-up water, causes
the rubber plug inside the valve to
deteriorate and eventually fail.

Approvals:
CSA C/US Certified to Canadian Standards
Association and Underwriter's Laboratories
Standards.

MODELS

V8043 (Straight through, Normally Closed)
   V8043A: Leadwires

V8043E: Leadwires and End Switch
V8043F: Terminal Board and End Switch

2

V8043A,E,F 5000 Series

ZONE VALVES

1

Patent Pending

CAUTION

    1. Disconnect power supply before

connecting wiring to prevent electrical
shock or equipment damage.

    2. Normally it is not necessary to remove

the actuator from the valve body during
installation. If the valve must be
disassembled, be certain that it is
reassembled with the water flow in the
direction of the arrow. Reversal of the
actuator results in damage to the gear
train.

    3.  On 24V systems, never jumper the

valve coil terminals even temporarily.
This can burn out the heat anticipator in
the thermostat.

INSTALLATION

When Installing this Product…

    1. Read these instructions carefully. Failure

to follow them could damage the product
or cause a hazardous condition.

    2. Check the ratings given in the

instructions and on the product to make
sure the product is suitable for your
application.

Fig. 1 - Mounting Dimensions in in. (mm in Brackets)

    3. Installer must be a trained, experienced

service technician.

    4. After installation is complete, check out

product operation as provided in these
instructions.

Location
    Install the valve in an area with adequate
clearance to:

- Move the manual opening lever on the

side of the actuator

- Remove the actuator cover
- Wire the actuator
- Replace the actuator motor

   The valve location should be in an area
where the temperature does not exceed the
maximum valve operating ambient
temperature and fluid temperatuare.

Manual Lever

The V8043 normally closed valves can be

opened manually by moving the manual lever
slowly and firmly to the MAN. OPEN position
and pushing up to the stop. The stop permits
the valve to be locked in the open position.
The valve returns to automatic position when
it is energized.

HEIGHT NEEDED TO REMOVE COVER.

DIMENSIONS FOR 1/2 IN. COPPER TUBING.

DIMENSIONS FOR 3/4 IN COPPER TUBING.

DIMENSIONS FOR 1 IN. COPPER TUBING.

4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL
 BOARD ENCLOSURE.

V4034B AND V8043B VALVES THAT ARE
 NORMALLY OPEN IN THE DE-ENERGIZED 
POSITION HAVE NO MANUAL LEVER. 

REFER TO MOUNTING INSTRUCTIONS.

OPENING FOR 1/2 IN. CONDUIT ON MANUAL 
LEVER SIDE FOR V4043, V8043.

1

2

3

4

5

6

7

8

M10175.A4

AUTO

MAN OPEN

A

B

8

1

6

5

2

3

4

V4043, V8043 SWEAT COPPER CONNECTION MODELS

2-3/8

(60)

7/8 DIA.
(22)

1-1/2

(38)

5-1/4
(133)

15/32
(12)

IN

OUT

3-1/2 (89)

1-3/4

(44)

3/8

(10)

1-3/4

(44)

1-5/16

(33)

1-3/8
(35)

2-5/8
(66)

2-3/4
(70)

1-11/16

(43)

3-3/8

(86)

7

0.570205s