60-2099-8

V4062A,B,D

HI-LO-OFF Fluid Power

Gas Valve Actuator

PRODUCT DATA

® U.S. Registered Trademark
Copyright © 1998 Honeywell Inc.   •   All Rights Reserved

APPLICATION

The V4062 Gas Valve Actuator in combination with a V5055
or V5097 Gas Valve provides three-position control of the
gas supply to commercial and industrial burners.

FEATURES

When energized, the V4062 Actuator opens the V5055/
V5097 Gas Valve to the low-fire position. The actuator
opens the valve to the fully open position when the
line voltage contacts are made.

When used with the V5055, V5097 or VE5000 Gas
Valve, the combination is rated for final safety shutoff
service.

Although the V4062 can be used with all V5055 or
V5097 Valve models, the V5055/V5097B with
characterized guide is recommended for optimum
control and low-fire repeatability

The standard model has an opening time of
26 seconds at 60 Hz, or 32 seconds at 50 Hz. A fast-
opening model is available, with timings of
13 seconds at 60 Hz, or 16 seconds at 50 Hz.

Maximum closing time is one second, which meets
code, standard, insurer requirements.

Damper shaft models are available with or without
spring return; shaft extends out both sides and rides
in Delrin bushings; used with standard damper crank
arm (part no. 7616BR).

Red OPEN indicator attached to the actuator stem
shows when the valve is even slightly open; yellow
SHUT indicator on the valve stem shows only when
the gas valve is fully closed.

Ambient temperature range is -40

° to 150°F (-40° to

66

°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for

50 Hz and 50/60 Hz models.

Models available with factory adjusted, field-
adjustable, single-pole-double throw (spdt) auxiliary
switch rated at 1/2 hp (0.37 kW). Auxiliary switch can
be added in the field.

Low-fire position is adjustable with adjusting wrench,
part no. 135796 (included with the actuator).

Standard enclosure meets NEMA 1 (IP30) general
purpose requirements.

V4062/V5055C,E and V4062/V5097C,E combinations
available with a proof-of-closure switch and double
valve seal (valve seal overtravel interlock) to meet
specific code/standard/insurer requirements.

Model available to be used with series 60 floating
type controller.

Model available with adjustable maximum flow
switch.

Contents

Application ..........................................................................

1

Features ..............................................................................

1

Specifications ......................................................................

2

Ordering Information ...........................................................

2

Installation ...........................................................................

4

Wiring ..................................................................................

5

Adjustments ........................................................................

6

Operation ............................................................................

7

Service and Checkout ........................................................

8