INSTALLATION INSTRUCTIONS

69-1486-1

T8411R Electronic

Heat Pump Thermostat

The T8411R Heat Pump Thermostat provides 24V 

control of two-stage heating and one-stage cooling heat 
pump system with manual changeover from heat to cool. 

First stage heating and cooling cycle rates are fixed at 
3 cph. Second stage heating cycle rate is selectable at 

3, 4, 5, 6, 9 or 12 cph. Temperature indication can be set 
for °F or °C. 

The T8411R Heat Pump Thermostat is powered directly 

from the system transformer. Batteries are not required 
because setpoints are held permanently by non-volatile 

memory.

The T8411R includes a thermostat, wallplate (for wiring 
and mounting thermostat), and owner’s guide. A 7 3/8 in. 

x 5 3/4 in. (188mm x146 mm) decorator cover plate (for 
covering wall marks) is available separately. Order 

Honeywel  part no. 209649A (taupe color).

MERCURY NOTICE

If this control is replacing a control that contains 

mercury in a sealed tube, do not place your old 
control in the trash.

Contact your local waste management authority 

for instructions regarding recycling and the 
proper disposal of an old control containing 

mercury in a sealed tube.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazard-
ous condition.

2. Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application.

3. Instal er must be a trained, experienced service 

technician.

4. After instal ation is complete, check out product 

operation as provided in these instructions.

CAUTION

Electrical Shock or Equipment Damage 
Hazard.

Can shock individuals or short equipment 
circuitry.

Disconnect power supply before installation.

Location
Install the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature. 

See Fig. 1. Do not install the thermostat where it can be 
affected by:

— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.

— radiant heat from the sun or appliances.
— concealed pipes and chimneys.

— unheated (uncooled) areas such as an outside wal  

behind the thermostat.

This thermostat is a precision instrument and was 

carefully adjusted at the factory. Handle it carefully.

Mounting Wallplate to Wall

IMPORTANT

Level only for appearance. The thermostat func-
tions normal y even when not level.

Mount wal plate, T8411R and the screws provided (see 

Fig. 2) as fol ows:

1. Place the wal plate at the desired location on the 

wal .

2. Use a pencil to mark the mounting holes.

3. Remove the wallplate from the wall and drill two 

3/16 in. holes in the wal  (if drywall) or two 7/32 in. 

holes for firmer material such as plaster or wood.

4. Gently tap the anchors (provided) into the holes 

until flush with the wal .

5. Position the wallplate over the holes.

6. Pul  the thermostat wire through the wallplate 

entrance hole.

7. Fasten the wal plate to the wall using the anchors 

and screws provided.