INSTALLATION INSTRUCTIONS

60- 0915- 4

L4006A,B,E,H

Aquastat® Controllers

APPLICATION

These boiler-mounted, immersion type control ers 

operate in response to temperature changes in hydronic 
heating systems.

L4006A breaks the circuit on a temperature rise to the 

control setting. It is used for high limit or low limit control. 
When used as a controller or as a low limit, a separate 

high limit must be used.

L4006B makes the circuit on a temperature rise. It is 
used as a circulator control er, delaying circulator 

operation when boiler water temperature is below the 
control setting.

L4006E,H includes a trip-free manual reset switch. 

These models are designed to break the control circuit 
whenever the temperature of the controlled medium 

reaches the high limit setting. A reset button on the front 
of the case must be pressed to re-establish the control 

circuit. L4006H also includes bracket and clamp for 
surface mounting on pipe or tank.

A plastic bag of heat-conductive compound is included 

with the L4006A,B,E Aquastat® Control ers for use when 
the sensing bulb is inserted into a wel  designed for a 

large bulb than the one used on the L4006A,B,E. A 
124904 Well Adapter, for use on old wells that do not fit 

the L4006A,B,E immersion well clamp, can be ordered; 
see form 68-0040, Wells and Fittings for Temperature 

Controllers.. A setting stop is included to prevent setting 
above a desired temperature on limit.

If a well adapter or other accessories are needed, refer to 

form 68-0040, Wells and Fittings for Temperature 
Controllers, for part numbers and ordering information.

INSTALLATION

When Installing This Product…

1. Read these instructions carefully. Failure to follow 

them could damage the product or cause a 
hazardous condition.

2. Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application.

3. Installer must be a trained, experienced service 

technician.

4. After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Electrical Shock Hazard.

Can cause serious injury, death or equipment 
damage.

Disconnect the power supply before beginning 
installation to prevent electrical shock or 

equipment damage.

Installing Immersion Well Models 
(L4006A,B,E)

IMPORTANT

Obtain the best thermal response with a well 
that snugly fits the sensing bulb. The bulb 

should be inserted until it rests against the 
bottom of the well. Use a wel  of correct length 

and bend the tubing, if necessary, to provide 
enough force to hold the bulb against the 

bottom of the well. Do not make a sharp bend in 
the tubing. A sharp bend can produce a break in 

the tubing and cause a loss of fil . This condition 
will cause the high and low limit controls to be 
made continuously.

If the well is not a snug fit on the bulb, use the 

heat-conductive compound as fol ows. Fold the 
plastic bag of compound lengthwise and twist 

gently. Snip the end of the bag and insert into 
the wel . Slowly pul  out the bag while squeezing 

firmly to distribute the compound evenly in the 
wel . Insert the bulb into the well. Bend the 

tubing, if necessary, to provide force to hold the 
bulb against the bottom of the wel  and to hold 

the out end of the bulb in firm contact with the 
side of the well. Wipe off any excess compound.

NOTE: Some models have an adjustable capillary 

tubing length to 3 inches (76 mm). In these 
models, pul  out extra tubing from inside the 

case, if needed. 

Fol ow the boiler manufacturer instructions, if available; 
otherwise, proceed as follows.