INSTALLATION INSTRUCTIONS

62-3075EFS-03

®

C

US

AM-1 Series™

PROPORTIONAL THERMOSTATIC MIXING AND DIVERTING 

VALVE STANDARD AND “C” TEMPERATURE RANGE MODELS - 

NPT, UNION SWEAT, THREAD, CPVC AND PEX MODELS

APPLICATION

The AM-1 Series™ family of quality valves in a variety of 

temperature ranges and connections, for master mixing or 

diverting applications.

SPECIFICATIONS

Temperature Range:

C Model: 70°F–120°F (21°C–49°C)

Standard Model: 70°F–145°F (21°C–63°C)

Connections:

Straight-through design (HOT and COLD at same level).

Construction:

Nickel plated brass construction. EPDM o-rings. Made in 

USA.

Lead Free Plumbing Code Compliance:  The wettable sur-

faces of lead free models contain less than .25% of lead by 

weighted average

Operating Pressure: 150 psi (1034 kPa) maximum.

Operating Temperature: 212 °F (100 °C) maximum.

Patent Information: U.S. Patent No. 6,079,625.

INSTALLATION

IMPORTANT

Mounting must comply with all local codes.

NOTE TO INSTALLER: This product should be installed by a 

qualified individual, in accordance with local codes and 

ordinances. It is the responsibility of the installer to properly 

select, install and adjust these devices as specified in these 

instructions. For installations which require compliance with 

Building/Mechanical/Plumbing Codes, the appropriate AM-1 

Series™ valve must be chosen and installed, and the 

discharge temperature set and locked according to these 

instructions. AM-1 “C” Series models with the temperature 

range, 70°F–120°F (21°C–49°C) and "Standard" models with 

temperature range 70°F–145°F (21°C–63°C) are ASSE® 

1017 (point of source application) certified, and CSA®a and 

IAPMO® listed. These models shall be used to supply water to 

tubs, showers, bathing facilities and other outlets. These 

valves should be installed where they will be accessible for 

cleaning, servicing or adjustment.

ASSE 1017 Applications—Point of 
Source
These AM-1 Series models can be installed in any position 

consistent with the intended use. For domestic hot water 

supply, the valve must be installed as shown in Fig. 1. There 

shall be no shut-off valves installed between the cold water 

line and the cold water connection on the AM-1 Series valve. 

Check valves shall be installed as indicated for NPT models; 

all AM-1 models with union fittings are supplied with integral 

check valves on both the hot and cold ports. A cold water 

service valve may be installed, as indicated, between the cold 

water supply line to the distribution system and the cold water 

line supplying both the water heater and the AM-1 Series 

valve.

NPT

Union

a -UCPVC and -UPEX models are not CSA listed.