GE Alterrex Diode Fact Sheet

GE Generator Control & Protection Fact Sheet - Alterrex Diode.
Download
Page  of 4
4.8, 2261 votes
background image

GE
Energy

ALTERREX* excitation systems were supplied with large

steam-turbine generators that shipped between 1965 and 1992.

The system consisted of a second AC generator, commonly

referred to as the Alterrex alternator, attached to the main unit

shaft via a rigid coupling. The output of the Alterrex was then

rectified by a set of fixed diode-based rectifier bridges installed

in the Alterrex alternator “doghouse.” The system utilized a

dedicated loop from the unit stator water-cooling system to cool

the individual diode bridges. The bridges consisted of 12 or

24 press-pack diode modules delivering high performance

and reliability in an efficient form factor made possible by the

liquid cooling.

The Problem

Unfortunately, the non-conductive de-ionized water used by the

stator is corrosive. The corrosive nature of the cooling water and

years of continuous high velocity flow are the root-cause of most

of today’s maintenance problems. Specific maintenance issues

associated with the system cooling components include: thin

walling/erosion of the copper pipe used for supply lines and

manifolds; fitting erosion; braze leaks; Teflon (black) tubing

cracks; O-ring hardening; gate valve corrosion; and copper

migration within Teflon® (white) tubes. Aging electrical components

are also driving increased maintenance, as diode indicating lights

used for diagnostics fail more often than the diodes, causing

false failure indications and wasted maintenance time.

The Solution

After more than a 30-year average service life and advances in

material technologies, the original diode bridges can be replaced

with a modern power conversion system. GE has custom-

designed a new EX2100 Rectifier Bridge for a one-for-one

replacement of the original rectifier and mounting in the original

cubicle. The new diode bridge is available with a range of on-

and off-site services to ensure the right level of services to meet

plant personnel, budget and outage limitations.

ALTERREX* Rectifier Replacement

fact sheet

Also See for GE Alterrex Diode

0.605743s