background image

Expanded Operating Temperature 
Range—Information Update

Technical Specifications

 

NOTE: Dell now supports expanded operating temperature ranges for 

PowerEdge R710, R610, and T610, subject to expanded temperature ranges and 
hardware restrictions detailed below.

Environmental

Operating Temperature

Continuous 
operation

• 10 °C to 35 °C at 10% to 80% relative humidity (RH), 

with 26 °C dew point.

• De-rate maximum allowable dry bulb temperature by 

1 °C/300 meters above 900 meters (1 °F per 550 feet).

Expanded Operating 
Temperature Range

10% of annual 
operating hours

• 5 °C to 40 °C, 5% to 85% RH with 26 °C dew point.

• For temperatures between 35 °C and 40 °C, de-rate maximum 

allowable dry bulb temperature by 1 °C/175 meters above 
950 meters (1 °F per 319 feet).

1% of annual 
operating hours

• –5 °C to 45 °C, 5% to 90% RH with 26 °C dew point. 

• For temperatures between 40 °C and 45 °C, de-rate maximum 

allowable dry bulb temperature by 1 °C/125 meters above 
950 meters (1 °F per 228 feet).

NOTE: When operating in the expanded temperature range, 
ambient temperature warnings may be reported on the LCD and in 
the System Event Log.
NOTE: Do not perform a cold startup below 5 °C.
NOTE: The operating temperature specified is for a maximum 
altitude of 3,050 meters (10,000 feet).