Installation Instructions

581B036-072

581C024-060

SINGLE-PACKAGE ROOFTOP HEATING/COOLING

STANDARD AND LOW NOx UNITS

TABLE OF CONTENTS

Page

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1- Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . .

ROOF CURB

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SLAB MOUNT

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ALTERNATE UNIT SUPPORT

2

. . . . . . . . . . . . . . . . .

Step 2- Field Fabricate Ductwork

2

. . . . . . . . . . . . . . . . . . .

Step 3- Install External Trap for Condensate Drain

2

. . . . . . .

Step 4- Rig and Place Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . .

POSITIONING

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 5 — Install Flue Hood

4

. . . . . . . . . . . . . . . . . . . . . . . .

Step 6 — Install Gas Piping

4

. . . . . . . . . . . . . . . . . . . . . . . .

Step 7 — Make Electrical Connections

8

. . . . . . . . . . . . . . . .

FIELD POWER SUPPLY

8

. . . . . . . . . . . . . . . . . . . . . .

FIELD CONTROL WIRING

8

. . . . . . . . . . . . . . . . . . . .

HEAT ANTICIPATOR SETTINGS

8

. . . . . . . . . . . . . . .

Step 8 — Adjust Factory-Installed Options

16

. . . . . . . . . . .

PERFECT HUMIDITY™ ADAPTIVE

DEHUMIDIFICATION SYSTEM

16

. . . . . . . . . . . . . .

MANUAL OUTDOOR-AIR DAMPER

16

. . . . . . . . . .

CONVENIENCE OUTLET

16

. . . . . . . . . . . . . . . . . . . .

OPTIONAL ECONOMI$ER IV

18

. . . . . . . . . . . . . . . .

ECONOMI$ER IV STANDARD SENSORS

19

. . . . . .

ECONOMI$ER IV CONTROL MODES

20

. . . . . . . . .

Step 9 — Adjust Evaporator-Fan Speed

25

. . . . . . . . . . . . . .

PRE- START- UP

41

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START- UP

41

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE

45

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

55

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START- UP CHECKLIST

60

. . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be

hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,

or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of

cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working

on air-conditioning equipment, observe precautions in the

literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers

available for all brazing operations.
Recognize safety information. This is the safety- alert symbol

. When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety- alert symbol.

DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard

which could result in personal injury or death. CAUTION is used

to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to

highlight suggestions which will result in enhanced installation,
reliability, or operation.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal

injury or death.
Before performing service or maintenance operations

on unit, turn off main power switch to unit and install

lockout tag. Ensure electrical service to rooftop unit

agrees with voltage and amperage listed on the unit

rating plate.

!

WARNING

FIRE, EXPLOSION HAZARD
Failure to follow this warning could cause death and/or

property damage.
Disconnect gas piping from unit when leak testing at

pressure greater than 1/2 psig. Pressures greater than 1/2

psig will cause gas valve damage resulting in hazardous

condition. If gas valve is subjected to pressure greater

than 1/2 psig, it must be replaced before use. When

pressure testing field-supplied gas piping at pressures of

1/2 psig or less, a unit connected to such piping must be

isolated by manually closing the gas valve(s).

!

WARNING

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert

to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in

basepan of unit with insulation-side down. Seals around

openings must be tight. (See Fig. 1.)