APC SBP3000RM2U User's Manual

APC Computer Accessories User's Manual - SBP3000RM2U.
Download
Page  of 2
4.7, 1198 votes
background image

 

 

3-16kVA Service Bypass Panels 

©2009 APC by Schneider Electric, APC, the APC logo, and Smart-UPS are             

owned by Schneider Electric industries S.A.S American Power Conversion  

Corporation, or their affiliated companies. All other trademarks are property 

of their respective owners. 

990-1530B

 

 

Note: Read the safety information sheet before installation.  

Illustrations in this document may differ slightly from the actual hardware. 

Attention: This product is for use in a controlled environment. Refer to product 
specifications for environmental limits. 

RACK MOUNTING 

 

o Set SBP in the rack. If hardwiring is required, see Connecting Power 
section before screwing into the rack. 

 

 

WALL MOUNTING 

  

n

 

 

 

 

 

o Whenever possible, attach one top screw and one bottom screw into a wall stud. If stud 
mounting is not possible, use an expandable wall anchor. Screws are not included; .25” x 
2” lag bolts are recommended. 

 

 
 TOWER OPTION (FOR SMART-UPS RT SETUPS ONLY) 

n  Remove screw from the top and bottom rear of both the UPS and SBP. Install tie 
brackets and reattach screws.

  

 

 

 

o Unscrew and remove top cover of the 
UPS.

 

 

p Attach bracket to top of UPS and SBP. 

 

 

q Reattach top cover of the UPS. 

 

 
 

 

 
Note: The SBP5000RMI2U, when used in conjunction with an SURT3000XLI or SURT5000XLI UPS in a 
tower configuration without an external battery pack (SURT192XLBP), is suitable for mounting on 
concrete or other non-combustible smooth surfaces only.

 

 

 

USER CONFIGURABLE 
Attention: When using an online UPS, put the UPS in automatic bypass mode before 
rotating the SBP switch. 

1. Normal: Power is directed from the utility outlet, through the Bypass Panel and UPS, 
and to connected equipment. For use during normal UPS operation. 
 
2. Test:
 Power supplied to the UPS is not output. Use when tests are being conducted on 
the UPS, and connected equipment is not yet desired. 
 
3. Bypass:
 Power from the utility outlet is filtered through the Bypass Panel, and to the 
connected equipment. Use to bypass the UPS, when functioning improperly. 

 

Note: While operating in ‘Test’ or ‘Bypass’ mode, power to the connected equipment is 
not conditioned by the UPS.  At this time, the “Equipment Protection Policy” is not valid. 

IDENTIFYING THE PANEL  
Service Bypass Panels will differ. Refer to chart for unit specifications.   

Note: HW= Hardwire 

Service Bypass 

Panel 

Corresponding 

UPS Systems 

Bypass

Input 

UPS 

Input 

UPS 

Output 

PDU 

Panel 

SBP3000RM2U 

100-120V Smart-UPS 

3kVA 

L5-30P 

L5-30R 

L5-30P 

(2) 5-20R, 

(6) 5-15R 

SBP5000RMT2U 

200/208/240V  

Smart-UPS 3-4.5kVA 

L6-30P 

L6-30R 

L6-30P 

(2) L6-20R, 

(2) L6-30R 

SBP5000RMI2U

230V Smart-UPS  

3-5kVA 

C20/HW 

C19/HW 

C20/HW 

(2) C19, 

(8) C13 

SBP6KRMT2U

** 

200/208/240V 

Symmetra 2-6kVA 

L6-30P/ 

HW 

L6-30R/ 

HW 

L6-30P/ 

HW 

(1) L6-20R, 

(2) L6-30R 

SBP6KRMI2U 

230V Symmetra  

2-6kVA 

HW 

HW 

HW 

(4) C19 

SBP3000 

100-240V Smart-UPS
3-5kVA with 30A HW

input/output 

available 

HW 

HW 

HW 

HW 

SBP10KRMT4U 

200/208/240V  

Smart-UPS RT  

7.5-10kVA 

HW 

HW 

HW 

(3) L6-20R, 

(3) L6-30R 

SBP10KRMI4U 

230V Smart-UPS RT 

7.5-10kVA 

HW (3Ph 

or 1Ph) 

HW (3Ph 

or 1Ph) 

HW 

(8) C13, 

(2) C19 

SBP16KP 

200-240V  

Symmetra LX 

4-16kVA 

HW (3Ph 

or 1Ph) 

HW (3Ph 

or 1Ph) 

HW 

HW 

SBP16KRMI4U 

220-240V  

Symmetra LX 

4-16kVA 

HW (3Ph 

or 1Ph) 

HW (3Ph 

or 1Ph) 

HW 

(3) 30A HW 

SBP16KRMP4U 

200/208/240  

Symmetra LX 

4-16kVA 

HW 

HW 

HW 

(6) L14-30R 

SBP16KRMP4U-HW 

200/208/240  

Symmetra LX 

4-16kVA 

HW 

HW 

HW 

(1) L14-30R, 

(3) L5-20R,  

(1) 100A HW 

*For loads exceeding 3kVA, hardwiring is necessary. 

  **For loads exceeding 5kVA, hardwiring is necessary. 

 

 

x4

x4 

x4 

x8 

Rear

Front

x1 

x4 

x8 

x2 

x2 

x2 