APC Back-UPS BX1300G User's Manual | Page 6

APC Power Supply User's Manual - Back-UPS BX1300G.
Download
Page  of 10
4.3, 1107 votes
background image

Installation and Operation  Back-UPS BX1300G/BN1350G/BX1500G

6

Modes of operation

Press DISPLAY to scroll through the display screens.

Status indicators

System faults

On Line Mode

On Battery Mode

Input Voltage

Estimated runtime in minutes

Counter

Power Event Counter 

Estimated run time

Output Voltage 

Load in Watts 

Input Voltage 

Load in % 

Load in Watts

Output Voltage

Load in %

Output Frequency

Output Frequency

Status

LED 

Audible Alarms

Audible Alarm Terminates

Overload 
An overload condition has occurred 
while operating on AC or battery power.

Constant tone

The alarm stops when nonessential 
equipment is disconnected from the 
Battery Backup outlets or the Back-UPS 
is turned off.

On Battery
The Back-UPS is supplying battery 
power to the Battery Backup outlets.

Beeps 4 times every 30 

seconds.

The beeping stops when AC power is 
restored or the Back-UPS is turned off.

Low Battery
The Back-UPS is supplying battery 
power to the Battery Backup outlets and 
the battery is near a total discharge state.

Continuous beeping

The beeping stops when AC power is 
restored or the Back-UPS is turned off.

F01

On-Battery Overload

Turn the Back-UPS off. Disconnect non-essential 
equipment from the Battery Backup outlets and then 
turn Back-UPS on.

F02

On-Battery Output Short

Turn the Back-UPS off. Disconnect non-essential 
equipment from the Battery Backup outlets and then 
turn Back-UPS on.

F03

On-Battery Xcap Overload

Faults F03-F09 are not user serviceable. Contact APC 
Technical Support for assistance.

F04

Clamp Short

F05

Charge Fault

F06

Relay Welding

F07

Temperature

F08

Fan Fault

F09

Internal Fault