Dry Contact I/O Accessory (AP9810) Technical Guide

Overview

The APC® Dry Contact I/O Accessory provides a hardware interface for connecting the host device 
of a Network Management Card 2 (AP9631 or AP9635) with peripheral devices. The Dry Contact 
I/O Accessory includes:

•  Inputs (labeled Zones A and B) for two dry contact devices

•  One 12 V, 25 mA power output (labeled Pwr)

•  One Form C relay (relay outputs labeled Output).

Dry Contact I/O Accessories connect to Universal I/O ports on your Management Card 2: AP9635 
includes one port and AP9631 includes two ports. Through your Management Card 2 software 
interface, you specify which alarms will cause a change in the state of the Form C relay. You also set 
the actions that will occur at the host due to a change in state of your dry contact devices.

Installation

Install the Dry Contact I/O Accessory using the details below. Connect devices to the screw terminal 
block using the following subsections. 

Note: The Management Card 2 must have application firmware v5.0.2 or greater. For 
details on upgrading the Management Card 2 firmware, see the user’s guide on the 
Network Management Card Utility CD or on the APC Web site (www.apc.com).

Note: If you are using PowerChute Network Shutdown (PCNS) and if your Management 
Card 2 has two Universal I/O ports, you must connect the Dry Contact I/O Accessory to 
Universal I/O port 2. PCNS supports only one Dry Contact I/O Accessory.

Item

Description

Screw terminal block; accepts 16 AWG to 28 AWG wires

Dry Contact I/O Accessory

25.4 cm (1 ft) CAT-5E RJ-45 patch cable used to connect the Dry Contact I/O 
Accessory to a Universal I/O port on a Management Card 2

dm

p0

1

1

4

a

Zone

Pwr

Output

B

A

NO

COM

NC

GND +1

2 NC

COM

NO

COM N

C