McQuay OM 751
Description of Operation
Space Temperature Set Points
The UVC uses the six occupancy-based temperature set points as the basis to determine the
Effective Set point Output. The effective set point is calculated based on the unit mode, the
occupancy mode, and the values of several network variables. The effective set point then is
used as the temperature set point that the UVC maintains.
Table 14: Default occupancy-based temperature set points
Networked Set Point Capability
The Space Temp Setpoint Input variable is used to allow the temperature set points for the
occupied and standby modes to be changed via the network; the unoccupied set points are not
affected by this variable.
Networked Set Point Offset Capability
The Networked Set Point Offset Input variable is used to shift the effective occupied and
standby temperature set points by adding the value of the Setpoint Offset Input variable to the
current set points; the unoccupied points are not affected by this variable. This variable is
typically set bound to a supervisory network controller or to a networked wall module having
a relative set point knob.
Use the keypad/display to make adjustments to the value of the Setpoint Offset Input variable.
See “Changing Set Points” on page 9.
Note – The keypad/display and the network both affect the Set Point Offset Input variable. Keep
in mind that changes to this variable are last-one-wins.
Networked Set Point Shift Capability
The Set Point Shift Input variable is used to shift the effective heat/cool set points. It typically
is bound to a networked supervisory controller or system that provides functions such as
outdoor air temperature compensation. All occupied, standby, and unoccupied set points are
shifted upward (+) or downward (–) by the corresponding value of the Set Point Shift Input
variable.
Note – The Set Point Shift Input capability is not available through the BACnet® interface.
Networked Space Temperature Sensor Capability
A networked space temperature sensor can be interfaced with the Space Temp Input variable.
When the Space Temp Input variable is used (valid value), it automatically overrides the hard-
wired space temperature sensor.
Temperature set point Abbreviation
Defaults
Unoccupied cool
UCS
82.4°F (28.0°C)
Standby cool
SCS
77.0°F (25.0°C)
Occupied cool
OCS
73.4°F (23.0°C)
Occupied heat
OHS
69.8°F (21.0°C)
Standby heat
SHS
66.2°F (19.0°C)
Unoccupied heat
UHS
60.8°F (16.0°C)
Related Manuals for American Standard UV05
-
Carrier Air Conditioners 24ABB3 Owner's Manual
2 pages
-
Vicks Air Conditioners V1200 Owner's Manual
2 pages
-
Trane Air Conditioners XL15i Owner's Manual
6 pages
-
Oreck Air Conditioners AIR12GU Owner's Manual
48 pages
-
Hunter Air Conditioners 30200 Owner's Manual
8 pages
-
Heat Controller Air Conditioners InverterFlex Series Owner's Manual
15 pages
-
Heat Controller Air Conditioners Patriot 80 Series Owner's Manual
4 pages
-
De'Longhi Air Conditioners PAC A110 Owner's Manual
18 pages
-
Trane Air Conditioners XE1000 Owner's Manual
6 pages
-
Mitsubishi Air Conditioners R410A User's Manual
18 pages
-
Sharp Air Conditioners CV10NH - 10,000 BTU Portable Air Conditioner Installation Manual
60 pages
-
White Rodgers Air Conditioners 1F78 User's Manual
6 pages
-
Goldstar Air Conditioners GWHD5000 Owner's Manual
44 pages
-
Duracraft Air Conditioners AMD-8500E User's Manual
8 pages
-
Trane Air Conditioners RTAC 140-400 User's Manual
252 pages
-
Haier Air Conditioners Commercial Cool CPN10XCJ User's Manual
36 pages
-
Haier Air Conditioners HSU-09HV03/R2(SDB) User's Manual
27 pages
-
Carrier Air Conditioners 30GB User's Manual
12 pages
-
De'Longhi Air Conditioners pinguino pac ct90 User's Manual
14 pages
-
Comfort-Aire Air Conditioners Air Conditioner PAD-121 User's Manual
19 pages
-
Kul Air Conditioners KU32085 User's Manual
28 pages
-
Trane Air Conditioners XR14 User's Manual
6 pages
-
Frigidaire Air Conditioners FFRH0822R1 Installation Instructions
6 pages
-
Arctic King Air Conditioners WINDOW/WALL TYPE ROOM AIR CONDITIONER User's Manual
20 pages