McQuay OM 751
Description of Operation
Emergency Heat Mode (Super State)
The Emergency Heat mode is provided for situations where the UVC is in a mode that does
not normally allow heating, such as OFF, Cool, Night Purge, or Fan Only. If Emergency Heat
mode is enabled, the UVC can automatically force itself into the Emergency Heat mode from
OFF, Cool, Night Purge, Fan Only, Purge, Pressurize, De-pressurize, and Shutdown.
Emergency Heat mode consists of UVC states: Full Heat [7] and Cant Heat [D].
Software model 05 does not have the primary or secondary heating devices. The UVC uses
auxiliary heat (if field provided and field connected) when emergency heat is required.
When the Emergency Heat mode becomes active, the UVC automatically determines which
state to make active, Full Heat [7], or Cant Heat [D], based on the transitions for each of those
states.
Figure 10: Emergency heat state diagram
Full Heat State (State 7)
The Full Heat [7] state is the “normal” state that the UVC goes into when Emergency Heat
mode is active. It is activated when the space temperature is lower than the EHS.
When Emergency Heat mode becomes active, the UVC goes into 100% heating until the space
temperature raises to the EHS plus a fixed differential (5.4°F/3°C). In the Emergency Heat
mode, the space fan is set to high speed, and the OA damper operates normally.
If the UVC automatically forces itself into the Emergency Heat mode from another mode
(e.g., Cool, Fan Only, etc.), then the UVC returns to the appropriate unit mode once the space
temperature rises to the EHS plus a fixed differential (5.4°F/3°C).
The UVC monitors the DAT to ensure it does not exceed DAHL. If the DAT does exceed
DAHL, then heating is set to 0% for a minimum of 2-minutes (fixed) and until the DAT drops
36°F (20°C) fixed differential below DAHL.
Cant Heat State (State D)
The Cant Heat [D] state is a “non-normal” state that the UVC can go into when Emergency
Heat mode is active. An IAT or DAT sensor fault during Emergency Heat mode causes the
UVC to make this state active.
When the Cant Heat state becomes active, the space fan remains at high speed as set during
the Full Heat state.
The UVC will remain in the Cant Heat state until heat becomes available.
Full Heat
Cant Heat
7
D
UVC Mode
≠
Emergency Heat
UVC Mode
=
Emergency Heat
Transition
point
Heat
≠
Available
Heat
=
Available
Emergency Heat Mode
Super State
Related Manuals for American Standard UV05
-
Carrier Air Conditioners 24ABB3 Owner's Manual
2 pages
-
Vicks Air Conditioners V1200 Owner's Manual
2 pages
-
Trane Air Conditioners XL15i Owner's Manual
6 pages
-
Oreck Air Conditioners AIR12GU Owner's Manual
48 pages
-
Hunter Air Conditioners 30200 Owner's Manual
8 pages
-
Heat Controller Air Conditioners InverterFlex Series Owner's Manual
15 pages
-
Heat Controller Air Conditioners Patriot 80 Series Owner's Manual
4 pages
-
De'Longhi Air Conditioners PAC A110 Owner's Manual
18 pages
-
Trane Air Conditioners XE1000 Owner's Manual
6 pages
-
Mitsubishi Air Conditioners R410A User's Manual
18 pages
-
Sharp Air Conditioners CV10NH - 10,000 BTU Portable Air Conditioner Installation Manual
60 pages
-
White Rodgers Air Conditioners 1F78 User's Manual
6 pages
-
Goldstar Air Conditioners GWHD5000 Owner's Manual
44 pages
-
Duracraft Air Conditioners AMD-8500E User's Manual
8 pages
-
Trane Air Conditioners RTAC 140-400 User's Manual
252 pages
-
Haier Air Conditioners Commercial Cool CPN10XCJ User's Manual
36 pages
-
Haier Air Conditioners HSU-09HV03/R2(SDB) User's Manual
27 pages
-
Carrier Air Conditioners 30GB User's Manual
12 pages
-
De'Longhi Air Conditioners pinguino pac ct90 User's Manual
14 pages
-
Comfort-Aire Air Conditioners Air Conditioner PAD-121 User's Manual
19 pages
-
Kul Air Conditioners KU32085 User's Manual
28 pages
-
Trane Air Conditioners XR14 User's Manual
6 pages
-
Frigidaire Air Conditioners FFRH0822R1 Installation Instructions
6 pages
-
Arctic King Air Conditioners WINDOW/WALL TYPE ROOM AIR CONDITIONER User's Manual
20 pages